American Power Conversion MX28B4800 MX28B1200/2400 MX28B1200/4800 -48 VDC User’s Manual, Page

Models: MX28B2400 MX28B4800

1 70
Download 70 pages 19.33 Kb
Page 46
Image 46

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

LVD 1 or 2 Option

Must be set to “Enable” if the unit has an LVD. If

LVD Option

m+

Security Level {1}

the unit has an LVD, but it is disabled, the

Enable

 

[MODULES/LVD/SET-ALM]

controller will not disconnect the LVD.

 

 

LVD 1 or 2 Reset

LVD Reset (reconnect) threshold voltage.

LVD Reset

m+

Security Level {1}

 

-48.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD 1 or 2 Trip

LVD Trip (disconnect) threshold voltage.

LVD Trip

m+

Security Level {1}

 

-42.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD Alarm

The output relay that is energized when the

LVD Open Alm m+

Security Level {1}

controller opens the LVD. If unit has a battery

Minor

 

[MODULES/LVD/SET-ALM]

LVD, no power will be available to turn on any

 

 

 

Output Relays.

 

 

Model Programming

Model type number for the MX28B DC power

Model

m+

Security Level {2}

plant. Choose the MX28B-1200 if you have the

MX28B-1200

[SYSTEM/SETUP]

2500 Amp battery shunt. Choose the MX28B-

 

 

 

4800 if you have the 5000 Amp battery shunt.

 

 

 

NOTE: Changing the model number causes the

 

 

 

system to reinitialize.

 

 

OEM R Gain

Voltage gain adjustment for factory calibration of

OEM R Gain

m+

Security Level {2}

system voltage readings/settings.

1.000

V

[OEM]

 

 

 

OEM R Offset

Voltage offset adjustment for factory calibration of

OEM R Offset

m+

Security Level {2}

system voltage readings/settings.

0.000 V

[OEM]

 

 

 

OEM S Gain

Current gain adjustment for factory calibration of

OEM S Gain

m+

Security Level {2}

battery current readings/settings.

1.000 A

[OEM]

 

 

 

OEM S Offset

Current offset adjustment for factory calibration of

OEM S Offset

m+

Security Level {2}

battery current readings/settings.

0.0 A

[OEM]

 

 

 

Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped” to activate

Out-Rly 1 Alm m+

Security Level {1}

other output relays (“Ignore” activates no

Ignore

 

[SYSTEM/OUT-RLY/RLY-

additional relays).

 

 

MAP]

 

 

 

 

 

 

Output Relay 6 Alarm

Output Relay 6 Alarm can be “mapped” to activate

Out-Rly 6 Alm m+

Security Level {1}

other output relays (“Ignore” activates no

Ignore

 

[SYSTEM/OUT-RLY/RLY-

additional relays).

 

 

 

MAP]

 

 

 

Output Relay 1 Alias

An alternate name (alias) can be assigned to

Out-Rly 1

m+

Security Level {1}

Output Relay 1 if desired.

Relay

1

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

 

 

An alternate name (alias) can be assigned to

 

Output Relay 6 Alias {1}

Output Relay 6 if desired.

Out-Rly 6

m+

[SYSTEM/OUT-RLY/ALIAS]

 

Relay

6

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 41

Page 46
Image 46
American Power Conversion MX28B4800, MX28B2400 manual MX28B1200/2400 MX28B1200/4800 -48 VDC User’s Manual, Page