N E T L I N X C O N T R O L C A R D S

NetLinx Control Cards serve as flexible, modular building blocks for creating advanced control applications. Up to 12 Control Cards can be inserted into the NXF NetLinx CardFrame’s front-access control slots or supplied in an NXS-NMS NetModule Shell enclosure for stand-alone operation.

NetLinx Control Cards can meet a wide variety of control needs, including multi-port RS-232/422/485, IR/Serial, Input/Output, Relay, Voltage, and Volume control. Every NetLinx Control Card includes a full array of LED status indicators at the front, easily viewable from the NetLinx enclosure’s translucent cover. Whether in a CardFrame or NetModule Shell, NetLinx Control Cards operate directly on the high-speed ICSNet data bus.

NXC-I/O10

Input/Output Card, 10 Channels

FG2021

The NXC-I/O10 Input/Output Card provides 10 Input/Output channels and LED feedback. It acts as a logic-level input and responds to switch closures or voltage level (high/ low) changes.

FEATURES

Provides 10 Input/Output control channels and front-panel feedback

Acts as logic-level switch or input, senses high and low voltage states in voltage mode

OPERATION

I/O 1-10: 10 I/O channels

STATUS 1-10: ONE LED FOR EACH CHANNEL

Yellow LED for on status

Green ICSP status LED

WIRING:

3.5 mm captive-screw terminals

NXC-VAI4

Voltage Output/Analog Input Card,

FG2025

The NXC-VAI4 Analog Voltage Card provides four independent analog-to- digital inputs and four independent digital-to-analog outputs, which are controllable over the ICSP network. Each port can be configured for a variety of DC input and output signals.

FEATURES

Inputs: Four high-impedance analog DC inputs

Outputs: Four analog DC outputs (user-configurable)

D/A, A/D conversion: A/D and D/A converters for analog sampling and control 8- or 10-bit; user selectable

Available input voltages: 0 V to +12 V

Available output voltages: -12 V to +12 V

The output voltage may be software-configured for any minimum and maximum levels between -12 and +12 VDC

Maximum output current = 60 mA.

Over-voltage protection to +28 VDC

External reference: A user supplied external reference voltage can be used to set the maximum voltage range for the D/A outputs. The full analog output range is scaled to fit the maximum range set by the external reference.

Output voltage may be set to any level between 0-12 VDC, referenced to the external reference voltage input and NXC-VAI4 power supply GND.

EXTERNAL REFERENCE INPUT: (EREF - ONE FOR EACH OUTPUT)

Maximum external reference input voltage = +12 VDC

Over-voltage protection to +28 VDC

INTERNAL REFERENCE OUTPUT: (IREF)

+5 V reference output, maximum current = 60 mA

This output is intended to drive a ground-referenced load

For more information about AMX products and services visit www.amx.com

CONFIDENTIAL INFORMATION © 2003 AMX Corporation. All rights reserved. AMX and the AMX logo are all trademarks of AMX Corporation.

11-03

AMX reserves the right to alter specifications without notice at any time. AMX does not assume responsibility for any errors or omissions.

 

Page 53
Image 53
AMX PTM-D15 manual T L I N X C O N T R O L C a R D S, NXC-I/O10, NXC-VAI4, FG2021, FG2025