Use the SMS (Short Messaging Service) icon to view or change the SMS settings used by your appliance.

For more information, see “Creating a send short message e-mail alert action” on page 123.

Note: This icon is available only if a modem that supports SMS messaging is installed in and configured for use with your appliance.

The SMS Configuration window consists of Basic, Advanced, and Status tabs. The Status tab displays the level and quality of the SMS signal. The following controls and data appear in the Basic tab:

Field

Description

 

 

SIM PIN / Confirm SIM PIN

For modems that use a SIM (subscriber identification module), specify

 

the PIN to unlock the SIM.

 

Note: For modems that do not have a PIN, this field is blank. For infor-

 

mation about your SIM PIN please contact your GSM/GPRS service

 

provider.

Service center (SMSC)

The address of the Short Message Service Center (SMSC) used by your

 

SMS service. The SMSC is an SMS server that sends messages. The

 

address for the SMSC is programmed into the SIM so you can leave

 

this field blank. Entering a value in this field overrides automatic

 

SMSC selection.

 

Note: For information about your SMSC please contact your GSM/

 

GPRS service provider.

Destination

Interrupt PPP when an SMS alert occurs

The e-mail destination address for an SMS message. The default value for this field is 0000000000. When an SMS message is sent to an e-mail destination address, the appliance puts the e-mail address at the beginning of the message and sends it to the Destination address. The SMSC receives the message, pulls out the e-mail address, and sends the remainder of the message to the e-mail address.

Note: For information about your SMS Destination please contact your GSM/GPRS service provider.

Enable this setting to allow SMS communication to override PPP communications, if your modem supports both SMS and PPP communications. Once the SMS message is sent, the PPP connection is reestablished.

Note: PPP connections that have been initiated using the Request Immediate Dial-up function are not interrupted, even if this checkbox is checked.