Output control external port settings

Output control external port settings

Select a device from the Output Control Configuration window and click External Ports. To modify devices connected to your output control devices:

1. Select the output control action to assign to the corresponding port from Relay Output Type.

Note: Output control actions do not apply for devices wired between the NO and NC terminals. These devices have an always open state.

The following output control actions are available when the output control device is wired between the NO (Normally Open) and COM terminals on the appliance:

Action

Description

 

 

None

No output action is associated with this port.

One-Second Button

When activated, a normally closed (NC) relay is switched to an

(NC)

open state for 1 second, and then switched back to closed.

One-Second Button

When activated, a normally open (NO) relay is switched to a

(NO)

closed state for 1 second, and then switched back to open.

Switch (NC)

When activated, a normally closed (NC) relay is switched to an

 

open state.

Switch (NO)

When activated, a normally open (NO) relay is switched to a

 

closed state.

Ten-Second Button

When activated, a normally closed (NC) relay is switched to an

(NC)

open state for 10 seconds, and then switched back to closed.

Ten-Second Button

When activated, a normally open (NO) relay is switched to a

(NO)

closed state for 10 seconds, and then switched back to open.

Reboot Button

When activated, power to the outlet is interrupted for 10 seconds,

 

and then restored.