Defining State Thresholds

To define a threshold:

1.Double-click the Camera Pods, Sensor Pods, or Scanned Devices icon.

2.Click Sensors... to open the Sensor Configuration window.

3.To define a threshold, select a sensor from the Sensors list. Defined thresholds for the sensor, if any, appear in the Thresholds list.

4.Click Add... to open the Select Threshold Type window.

5.Select the threshold to define and click OK. The Add Threshold window opens.

6.Type a name for the threshold in Threshold name.

7.Specify threshold settings in the Basic tab:

a.For an Alert State For Time Threshold, select an Alert State. In Time Allowed in Alert State, enter the number of seconds that the reported value can be in the Alert State before an alert condition is generated.

b.For Alert State Threshold, select an Alert State that causes an alert condition.

c.For a State Mismatch For Time Threshold, select a Normal State for the device. In Time Allowed in Alert State, enter the number of seconds that the reported value can be in a state other than the Normal State before an alert condition is generated.

d.For a State Mismatch Threshold, select the normal operational state for the device from Normal State.

8.For Rack Access sensors, the following thresholds are available:

a.Unscheduled Access Threshold - This is only available for Lock sensors and is enabled by default. It creates an alert on unscheduled card, key, or remote access. If any of the other “Unscheduled” access thresholds are used (Card, Key, or Remote), this threshold should be removed from the sensor.

b.Door Forced Entry Threshold - This is only available for Door sensors and is enabled by default. If the door is open while the handle is down and the lock is locked, an alert is generated. It has one advanced setting - “Allow handle down while door open”. When this option is selected, returning the handle to the down position while the door is open will not generate an alert.

c.Handle Forced Entry Threshold - This is only available for Handle sensors and is enabled by default. If the handle is up while the lock is locked, an alert is generated.

d.Unscheduled Card Access Threshold - This is only available for Lock sensors and is not enabled by default. If a door is opened with a card but left open past that card’s access schedule, an alert is generated.

e.Unscheduled Key Access Threshold - This is only available for Lock sensors and is not enabled by default. If a lock is opened with a key, an alert is generated. If you want to enable key access without generating an alert (for example, during normal work hours), you will need to modify the threshold schedule, disable the threshold for the desired timeframe, and disable the default “Unscheduled Access Threshold”. A key unlock event will still be generated in the event log.