Bosch Appliances D9412GV3 4.0Installation, 4.1Installation Preparation, 4.2Enclosure Options

Models: D9412GV3 D7412GV3

1 76
Download 76 pages 25.33 Kb
Page 14
Image 14
Installation

D9412GV3/D7412GV3 Operation and Installation Guide

4.0

Installation

 

 

 

3.3.13 Ground Fault Detection Added Feature

When Ground Fault Detect is enabled (S4 closed), Points 1 to 8 can be used for non-powered fire- initiating devices such as heat detectors, four-wire smoke detectors, and pull stations. A D125B Powered Loop Interface or a D129 Dual Class A Interface Module is not required when connecting the non- powered fire-initiating devices to Points 1 to 8.

3.3.14 Conettix Functions

The D6600 Conettix System supports data network communications. Conettix allows the D6600 Receiver to connect to various network technologies including Ethernet and GPRS (General Packet Radio System). Connecting to a data network is possible using the COM4 or COM1 connection from the D6600 Receiver to the D6680 Network Adapter. Control panels can send reports through telephone lines, Ethernet, Token-Ring or GPRS networks to the D6600 receiver at the central station. Once events are received, they can then be issued to automation software or a network printer through a local area network (LAN) or wide area network (WAN).

Sending events to the central station over a LAN or WAN requires a network interface module (NIM), such as the DX4020. Sending events over GPRS requires

aspecial NIM, the ITS-DX4020-G.

3.3.15 Programming

Use the Remote Programming Software (RPS), or the local Programmers Menu, to program the D9412GV3 and D7412GV3 Control Panels. Refer to the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) for programming options.

3.3.16 Other Features

D9412GV3 and D7412GV3 Control Panels have many programmable features. Some of the features are listed below. Complete details on all features are in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).

Supervision of AC (primary power), battery (secondary power), Zonex and SDI buses, central processing unit (CPU), up to three printers, and two telephone lines

Automatic System Test Reports

Remote access for programming, diagnostics, and log uploads using the remote programming software (RPS)

Fire alarm verification

Programmable alarm output

Programmable relay output using the D8129 OctoRelay Module

Opening and closing windows

Skeds (scheduled events)

Limited local programming available in the Service Menu

4.0Installation

4.1Installation Preparation

This section contains a general installation procedure and refers to other sections of the document for detailed instructions.

Review this document and the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) before beginning the installation to determine the hardware and wiring requirements for the features used.

Have the following documentation available when reading through this guide:

D9412GV3/D7412GV3 Program Record Sheet (P/N: F01U170809)

Security System Owner’s Manual

(P/N: 71-06633-000) and GV3 Series Owner’s

Manual Supplement (P/N: F01U143082)

Installation manual for keypad or annunciator (D1255 all models, D1255RB, D1256, D1256RB, D1257, D1257RB, D1260 all models, or D720 all models)

Before installation, become familiar with the operation of RPS or the local Programmers menu.

4.2Enclosure Options

Mount the control panel assembly in any of the Bosch Security Systems, Inc. enclosures listed:

D8103 Universal Enclosure (tan)

D8109 Fire Enclosure (red)

D8108A Attack Resistant Enclosure (tan)

Refer to the D9412GV3/D7412GV3 Approved Applications Compliance Guide (P/N: F01U143069) to determine if the application requires a specific enclosure.

4.3Mounting Enclosure

1.Run the necessary wiring throughout the premises.

2.Mount the enclosure in the desired location. Use all five enclosure mounting holes. Refer to Figure 2.

3.Pull the wires into the enclosure.

Electromagnetic interference (EMI) can cause problems on long wire runs.

Bosch Security Systems, Inc. 10/10 F01U143070-03

14

Page 14
Image 14
Bosch Appliances D9412GV3 manual 4.0Installation, 4.1Installation Preparation, 4.2Enclosure Options, 4.3Mounting Enclosure