5.2.6Battery Discharge and Recharge Schedule

D9412GV3/D7412GV3 Operation and Installation Guide

5.0

Power Supply

 

 

 

Reset the control panel by momentarily placing the reset pin in the disable position. Refer to Figure 4 on page 16. The red Low Battery LED continues flashing until the control panel resets.

5.2.6Battery Discharge and Recharge Schedule

Table 6: Battery Discharge and Recharge Schedule

 

 

Discharge Cycle

 

AC Off:

AC Fail Report when AC fails, if

 

control panel is programmed to

 

report AC failure at occurrence.

13.9 VDC:

Charging float level.

13.8 VDC:

Charging status LED on.

12.0 VDC:

Low Battery and AC Fail Reports if

 

programmed. Low battery LED on.

<10.0 VDC: Battery load shed (processing functions continue if AC is present).

Recharge Cycle

AC On:

Load shed relay reset; battery

 

charging begins; Battery Trouble

 

and AC Restoral Reports sent.

13.7 VDC:

Battery Restoral Reports sent. Low

 

battery LED off.

13.9 VDC:

Changing status LED off; battery

 

float charged.

Table 7:

Charging Status and Low Battery LEDs

 

 

 

 

 

 

 

 

 

 

 

 

LED

 

 

Type

 

Color

State

Action

Charging Status LED

Yellow

 

Shows the charging status of the battery. Refer to Figure 9 on

 

 

 

 

page 24 for location.

 

 

Yellow

Off

Battery is fully charged.

 

 

 

 

If the battery is missing, shorted, or reversed, the Charging Status

 

 

 

 

LED is off, but the red Low Battery LED is flashing.

 

 

Yellow

On

Battery float charge is below 13.8 VDC. If AC is present, the

 

 

 

 

battery is charging.

 

 

 

 

Indicates the combined current draw from all outputs exceeds 1.4

 

 

 

 

A. This is normal under alarm conditions for non-fire systems with

 

 

 

 

sirens or bells drawing more than 1.4 A. If the LED lights regularly

 

 

 

 

for extended periods or does not go out, check the current draw

 

 

 

 

for devices connected to the power outputs. Refer to Section 6.0

 

 

 

 

Power Outputs on page 26 for instructions.

 

 

Yellow

Flash once per

System is checking the battery.

 

 

 

minute

 

Low Battery LED

Red

 

Shows the condition of the battery. Refer to Figure 9 on page 24

 

 

 

 

for location.

 

 

Red

Off

Battery is fully charged.

 

 

Red

On

Battery voltage dropped to between 12.0 VDC and 11.8 VDC.

 

 

 

 

LED turns off when voltage reaches 13.7 VDC.

 

 

Red

Flash

Battery is missing or shorted.

 

 

 

 

 

Bosch Security Systems, Inc. 10/10 F01U143070-03

25

Page 25
Image 25
Bosch Appliances D7412GV3 5.2.6Battery Discharge and Recharge Schedule, Charging Status and Low Battery LEDs, Power Supply