Bosch Appliances D7412GV3 11.3D279A Independent Zone Control, 11.4Keyswitch, Power at Keypads

Models: D9412GV3 D7412GV3

1 76
Download 76 pages 25.33 Kb
Page 57
Image 57
Figure 28: Power at Keypads

D9412GV3/D7412GV3 Operation and Installation Guide 11.0 Arming Devices

Figure 28: Power at Keypads

 

 

 

 

 

 

 

5

 

1

 

2

2

 

 

 

 

 

 

3

4

 

 

 

 

 

 

 

3

 

 

 

 

4

 

1 -

To control panel

4 -

Common

 

2 -

+12.0 VDC

5 - D8132 or external power supply

 

3 -

Data

 

 

 

11.3D279A Independent Zone Control

Any on-board or OctoPOPIT point can be programmed so that the D279A Independent Zone Control operates as independent point control (arming and disarming the point).

Refer to Point Assignments in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) for

programming information. Refer to the D279A Operation and Installation Instructions (P/N: 46458) for wiring and operation instructions.

11.4Keyswitch

11.4.1 Description

A maintained or momentary contact arming station (keyswitch) can be connected to master arm or disarm any of the areas in the system. The keyswitch is connected to an on-board or off-board point’s sensor loop. Relays can be programmed to activate arming status LEDs for keyswitch arming stations. Refer to Relays in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).

11.4.2 Programming

Refer to Point Assignments in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) for the correct programming for points used for keyswitches.

11.4.3 Installation

For maintained switches, connect the EOL resistor for the point at the keyswitch so that the switch opens the circuit when it operates. A short on the circuit produces an alarm if the area is armed and a trouble if it is disarmed. Refer to Figure 29 on page 58.

For momentary keyswitches, connect the EOL resistor at the keyswitch point so that when the keyswitch operates, it shorts the resistor. An open on the circuit causes an alarm if the area is armed and a trouble if it is disarmed. Refer to Figure 29 on page 58.

11.4.4Operation

Maintained Contact

If the point to which the keyswitch is connected is programmed for a maintained contact, an open on the arming circuit arms the area. All faulted points are force armed, regardless of the entry in the FA Bypass Max program item. Returning the circuit to normal disarms the area. Refer to Area Parameters and Point Assignments in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).

Bosch Security Systems, Inc. 10/10 F01U143070-03

57

Page 57
Image 57
Bosch Appliances D7412GV3 11.3D279A Independent Zone Control, 11.4Keyswitch, Power at Keypads, Description, Programming