12.4D9210B Wiegand Control Interface Module

D9412GV3/D7412GV3 Operation and Installation Guide 12.0 SDI Devices

12.4D9210B Wiegand Control Interface Module

The Bosch Security Systems, Inc. D9210B Wiegand Control Interface Module is a four-wire powered device providing connections for an access door point and door strike. The D9412GV3 can supervise eight Wiegand Control Modules, the D7412GV3 can supervise two. Each D9210B supports one door to control access. Programming allows each access door to be configured independently.

12.4.1 Access

Using Wiegand style cards or tokens, the D9210B can allow access for up to 996 cards or tokens on the D9412GV3, and up to 396 on the D7412GV3. User access authority can be configured to restrict access to certain doors or to certain periods of time. The reading of access cards, in addition to granting access, can control whether the system disarms. Used with the D9412GV3, the D9210B recognizes 249 master users by user name, passcode, and access authority. The D9210B recognizes 99 master users when used with the D7412GV3. Each master user supports three sub-users with unique cards or tokens having the same access level as the master user.

12.4.2 Switch Settings

Switches on the D9210B assign a unique address (1 to 8) to each module. Table 23 shows the correct switch setting for each D9210B address.

Table 23: Address Switch Settings for Access Control Module

 

 

 

 

 

 

 

Door Module

 

DIP Switch Settings

 

Addresses

 

 

 

 

 

 

1

2

3

41

52

62

1

ON

ON

ON

 

ON

ON

2

OFF

ON

ON

 

ON

ON

---------------D7412GV3 Maximum---------------

12.5SDI Addresses 88 and 92

SDI Addresses 88 and 92 are available with the D9412GV3 and D7412GV3 Control Panels and are used for several different applications. Only one device can be assigned to SDI Address 88 at a time. Likewise, only one device can be assigned to SDI Address 92 at a time.

12.5.1D9133DC Direct Connect Programming Module

Use the D9133DC Direct Connect Programming Module to handle local programming of the D9412GV3 and D7412GV3 Control Panels. In addition, the D9133DC allows diagnostic and history retrieval.

The D9133DC is not UL Listed, and cannot remain connected to the system for UL applications.

UL requires that the D9133DC be used for programming only.

D9133DC uses SDI 88 only.

Connecting the D9133DC

1.Configure D9133DC for SDI Address 88. To program the control panel when the reset pin is in the unlocked position, program Enable SDI RPS to Yes in the GV2AUX handler.

2.Connect D9133DC to Com Port 1 or Com Port 2 on the PC. The D9133DC has a DB-9 female serial connector. A null-modem cable must be purchased separately to connect the D9133DC to a PC.

3.Using 0.8 mm (22 AWG) or 1.2 mm (18 AWG) wire, connect the D9133DC SDI terminals (SDI PWR, SDI A, SDI B, and SDI COM) to the control panel’s SDI terminals (Terminals 29 to 32).

3

ON

OFF

4

OFF

OFF

5

ON

ON

6

OFF

ON

7

ON

OFF

8

OFF

OFF

1Switch 4, Fail Safe Mode:

ON

ON

OFF OFF OFF OFF

ON ON ON ON ON ON

ON ON ON ON ON ON

To send or receive the control panel’s program, place the Reset Pin in the Locked or Unlocked position.

Locking the Reset Pin when programming the control panel improves the uploading and downloading times.

ON = If SDI bus fails, relay energizes.

OFF = If SDI bus fails, relay de-energizes.

2Switches 5 and 6 must remain in the ON position.

Bosch Security Systems, Inc. 10/10 F01U143070-03