9.4.3Installation

D9412GV3/D7412GV3 Operation and Installation Guide

9.0

Off-Board Points

 

 

 

9.4.3Installation

For the most effective installation, use the following four-step process:

1.Set the OctoPOPIT switches. Refer to Section 9.4.4 Setting the OctoPOPIT Switches.

2.Physically mount the OctoPOPIT in the enclosure. Refer to Section 9.4.5 Mounting OctoPOPITs, page 45.

3.Wire the OctoPOPIT. Refer to Section 9.4.6 Wiring OctoPOPITs on page 45.

4.Wire the OctoPOPIT sensor loops. Refer to Section 9.4.7 OctoPOPIT Sensor Loops on page 49.

9.4.4Setting the OctoPOPIT Switches

The D8128D OctoPOPIT has two sets of DIP switches (Figure 19 on page 43). Use the DIP switches on the top of the unit (with the terminal strip along the left edge) to set the address for the OctoPOPIT. Use the DIP switches at the bottom of the unit to enable or disable individual points connected to the OctoPOPIT.

Address Switches

The switches on the D8128D OctoPOPIT set point assignments and line termination. These switches are easier to set before mounting the D8128D in the enclosure.

Switches 1, 2, 3, and 4 assign the OctoPOPIT sensor loops to point numbers on the control panel. Table 14 shows the OctoPOPIT switch settings for point assignments.

Switch 5 sets line termination. Refer to Table 15.

Table 14: D8128D OctoPOPIT Switch Settings for D9412GV3 and D7412GV3

 

 

 

 

 

 

 

 

ZONEX 1

D8128D Address Switches

 

ZONEX 2

Points 9 to

 

 

 

 

 

 

Points 129

127

1

2

3

4

 

5

to 247

9 to 16

ON

ON

ON

ON

 

*

129 to 136

17 to 24

ON

ON

ON

OFF

 

*

137 to 144

25 to 32

ON

ON

OFF

ON

 

*

145 to 152

33 to 40

ON

ON

OFF

OFF

 

*

153 to 160

41 to 48

ON

OFF

ON

ON

 

*

161 to 168

49 to 56

ON

OFF

ON

OFF

 

*

169 to 176

57 to 64

ON

OFF

OFF

ON

 

*

177 to 184

65 to 72

ON

OFF

OFF

OFF

 

*

185 to 192

 

 

 

 

 

 

 

 

73 to 80

OFF

ON

ON

ON

 

*

193 to 200

81 to 88

OFF

ON

ON

OFF

 

*

201 to 208

89 to 96

OFF

ON

OFF

ON

 

*

209 to 216

97 to 104

OFF

ON

OFF

OFF

 

*

217 to 224

105 to 112

OFF

OFF

ON

ON

 

*

225 to 232

113 to 120

OFF

OFF

ON

OFF

 

*

233 to 240

121 to 127

OFF

OFF

OFF

ON

 

*

241 to 247

*Line Termination Switch

For the D8128D OctoPOPITs assigned to Points 121 to 127, 241, and 247, set Point Input Switch 8 to the OPEN position.

D9412GV3 uses Points 9 to 127 on Zonex 1 and Points 129 to 247 on Zonex 2.

D7412GV3 uses Points 9 to 75 on Zonex 1 only.

Table 15: Switch 5 Settings for Line

Termination

 

 

 

 

 

Is a D8125 POPEX

Switch 5 Setting(s) on

 

Module connected?

D8128D OctoPOPIT(s)

 

No

 

Set Switch 5 of only one

 

 

D8128D to ON

 

 

 

 

Yes

Set Switch 5 of all

 

D8128Ds to OFF

 

 

 

Point DIP Switches

Each point connected to the D8128D is enabled by closing the respective DIP switch, or disabled by opening the DIP switch. For example, to disable a device connected to the P3 Terminal (Point 3), move DIP switch number 3 to the OPEN position.