9.4.2Listings

D9412GV3/D7412GV3 Operation and Installation Guide

9.0

Off-Board Points

 

 

 

9.4.2Listings

The D8128D OctoPOPIT Module is UL Listed for Local or Police Connected Burglary Alarm, Central Station Burglary Alarm, Household Burglary Alarm applications, and commercial fire applications (UL 864 and NFPA 72).

The D8128D is also suitable for fire supervisory applications, such as indicating circuit supervision (using the D192G Bell Circuit Supervision Module), sprinkler supervision, and valve tamper protection.

Requirements for Fire Initiation Applications

Non-powered, fire initiating devices such as pull-stations, heat detectors, and UL Listed four-wire smoke detectors can be connected directly to the point inputs on the D8128D.

For UL 864 Commercial Fire applications, refer to Installing Combination Fire and Intrusion Alarm Systems in the D9412GV3/D7412GV3 Approved Applications Compliance Guide

(P/N: F01U143069) for important information about combination fire and intrusion systems.

The D125B Dual Powered Loop Interface Module or the D129 Dual Class “A” Module zone outputs can be connected directly to the point inputs on the D8128D. Use the D125B to connect two-wire smoke detectors. Typically, the D129 is used for connecting waterflow switches.

The D125B or D129 and the OctoPOPIT can be mounted in the same enclosure with the control panel or in a separate enclosure connected to the control panel’s enclosure by a conduit not more than 6 m (20 ft.) in length.

Figure 19: D8128D OctoPOPIT Layout

1

2

3

4

1 2 3 4 5 6 7 8

P O I N T S

1 - Molex® connectors

2 - Address DIP switches

3 - Terminal strip

4 - Point DIP switches

Bosch Security Systems, Inc. 10/10 F01U143070-03