Bosch Appliances D7412GV3, D9412GV3 Installation, b.Press the ESC key. VIEW UNTESTED ? appears

Models: D9412GV3 D7412GV3

1 76
Download 76 pages 25.33 Kb
Page 19
Image 19
b.Press the [ESC] key. VIEW UNTESTED ? appears.

D9412GV3/D7412GV3 Operation and Installation Guide

4.0

Installation

 

 

 

5.To see the points that remain untested during the Service Walk Test:

a.Press [ESC] when point text appears. The display shows ## PTS TO TEST.

b.Press the [ESC] key. VIEW UNTESTED ? appears.

c.Press [ENT]. ## PTS UNTESTED appears.

d.Press [NEXT] to see a list of the points that have not yet been tested. Move through this list by pressing the [NEXT] key.

e.To resume the Service Walk Test, press [ESC]. ## PTS UNTESTED appears.

f.Press [ESC]. ## PTS TO TEST appears.

g.Resume testing points. To end the Service Walk Test, press [ESC] twice.

6.After the last point is tested, 0 PTS TO TEST appears. Press [ESC]. The display shows ALL PTS TESTED briefly before returning to idle text.

The Service Walk Test, when performed on a D7412GV3, cannot display “0 PTS TO TEST” because the D7412GV3 is physically unable to connect to the second POPEX Module (used for Points 129-247).

Automatic time-out returns the system to idle text: If there is no point or keypad activity for 20 min., the Service Walk Test ends automatically. The keypad returns to idle text.

Bosch Security Systems, Inc. 10/10 F01U143070-03