4.8Installing the Point Chart Label

D9412GV3/D7412GV3 Operation and Installation Guide

4.0

Installation

 

 

 

4.8Installing the Point Chart Label

The point chart label is required for fire systems with verifications points.

A point chart label is included in the literature pack. Install the point chart label for fire or combined fire- and-burglary systems that use verification points.

Use the D9412GV3/D7412GV3 Program Record Sheet (P/N: F01U170809) to gather the necessary information for completing the point chart. Fill out the label and install it on the inside of the enclosure door (refer to Figure 2 on page 15).

Avoid smearing the entries on the chart. Use the peel-off backing to press the label in place.

4.9Testing the System

After installing and programming the control panel, test the system completely. Test the control panel and all devices for proper operation.

Test after initially programming the control panel.

To meet UL 864 requirements, perform a full system test after any subsequent programming session.

Refer to Section 4.10 Service Walk Test on page 18 for complete Service Walk Test instructions.

Clear after Test: To clear the event memory and report buffer, momentarily close the reset pin. Events stored in the control panel’s event log are not cleared.

4.10Service Walk Test

The Service Walk Test differs from the standard Walk Test. In the standard Walk Test, POPITs whose switches are set for a point number not programmed in the control panel do not appear in the test. In the Service Walk Test, POPITs whose switches are set for a point number that is not programmed in the control panel do appear in the test.

The Service Walk Test allows a user to walk test all 246 points from a control-panel-wide keypad, regardless of the point index type.

A Service Walk Test can also be initiated by account- wide or area-wide keypads but test only those points that are within the scope of the keypad that initiated the function. The Service Walk Test does not test points in armed areas.

Only Walk Test Start and Walk Test End are reported to the central station.

The D9131A can be configured for local printing. Refer to the D9412GV3/ D7412GV3 Program Entry Guide (P/N: F01U170807).

During a Service Walk Test, the summary alarm and summary fire remain off, because there are no Fire or Burg alarm conditions to summarize. The P# Relay Response Type feature operates as programmed.

Service Walk Test Procedure.

Refer to Figure 5 on page 20 and Figure 6 on page 21 for Service Walk Test options. Refer to the Walk Test procedures in the GV3 Series Owner’s Manual Supplement (P/N: F01U143082) when using a D1260 or D1260B Keypad.

1.Choose a keypad to conduct the test. Ensure that the display shows the idle disarmed text.

2.Press the [MENU] key to enter the Function List. Press [NEXT] repeatedly until the SERVICE WALK ? prompt appears.

3.Press [ENT], or press [9][9] followed by [ENT] to reach the Service Menu to access the Service Walk Test.

The D7412GV3 does not include the Service Walk Test in the Service Menu. Enabling the Service Walk Test function in the Function List provides access to the Service Walk Test in the D9412GV3.

4.The display shows ### PTS TO TEST .Test the first detection device.

5.When a detection device is faulted, the keypad emits a brief tone and displays the point text of the point tested for 60 sec. After 60 sec, the display returns to the ### PTS TO TEST message.

Extra Points display default text: If the switches on a POPIT are set incorrectly to a point number that is not in the program for the control panel, the default text for that point number (PT ###) appears when the point is faulted. Refer to the control panel’s program record sheet for the default text for all points.