ELECTRICAL REQUIREMENTS

ELECTRICAL REQUIREMENTS

WARNING - If the power cord is ever damaged, it must be replaced by the manufacturer or its service agent with a special cord available from the manufacturer or its service agent in order to avoid a hazard.

Refer to Data Plate on the Brewer, and local/national electrical codes to determine circuit requirements.

WHI

N

BLU

L3

RED

L2

BLK

L1

GREENGREEN

120/208 and 120/240 volt ac three phase, 50/60 Hz models

BLK BLU

TO MACHINE

WHI

RED

 

L1

L2

L3

N

FROM POWER SOURCE

FOR SINGLE PHASE OPERATION MOVE BLU WIRE INTO TERMINAL BLOCK WITH BLACK WIRE. CONNECT INPUT WIRING TO:

L1, L2 & N FOR 120/208V & 120/240V MODELS,

L1 & N for 230V MODELS.

WHI

N

BLU

L3

RED

L2

BLK

L1

GREENGREEN

400/230V volt ac three phase,

50/60 Hz models

Note: This electrical service consists of 4 cur- rent carrying conductors (Neutral, L1, L2 and L3) and a separate conductor for earth ground.

Note: This electrical service consists of 4 cur- rent carrying conductors (Neutral, L1, L2 and L3) and a separate conductor for earth ground.

SYSTEM

 

 

VOLTAGE

V1

V2

208

208

120

240

240

120

L1, L2, L3, are the 3 phases

V1 = Phase to phase voltage, between any 2 phases.

V2 = Phase to neutral voltage, L1 to neutral must be 120V.

SYSTEM

 

 

VOLTAGE

V1

V2

400

400

230

230

 

230

L1, L2, L3, are the 3 phases

V1 = Phase to phase voltage, between any 2 phases.

V2 = Phase to neutral voltage, L1 to neutral must be 230V.

ELECTRICAL HOOK-UP

CAUTION – Improper electrical installation will damage electronic components. Damage caused by incorrect electrical connections is not covered by warranty.

1.An electrician must provide electrical service as specified in conformance with all local, state and federal electrical codes.

2.Using a voltmeter, check the voltage and color coding of each conductor at the electrical source.

NOTE - The brewer is shipped without a plug on the power cord. Qualified service personnel must select and install the proper UL listed grounding type attachment plug specified on the rear of the brewer.

3.Install the specified plug on the attached power cord.

4.Remove the front access panel to gain access to the terminal block.

5.Connect the brewer to the power source and verify the voltage at the terminal block before proceeding.

6.If plumbing is to be hooked up later be sure the brewer is disconnected from the power source. If plumbing has been hooked up, the brewer is ready for Initial Set-Up.