MOST FREQUENT PTAC SERVICE QUESTIONS

1.

Can remote thermostats be used on standard (AA)

No, only for use on remote control (RC) models.

 

models?

 

2.

Which remote thermostats are acceptable for use on

HH01AD045 Ð Manual changeover thermostat

 

52S products?

TSTATCCPAC01 Ð Programmable AC thermostat

 

 

TSTATCCPHP01 Ð Programmable HP thermostat

3.

How many 52S series units can be controlled by one

Only 2.

 

remote thermostat?

 

4.

What is the vent capacity of the 52S products?

35 cfm (standalone). Capacity can be increased

 

 

with the use of an external exhaust fan.

5.

How do the 52S series models handle condensate

By using a slinger ring to evaporate the water on

 

removal?

the outdoor coil, and by using an optional acces-

 

 

sory drain kit.

6.

At what temperature will the outdoor (defrost)

15 F coil temperature/approx 35 F ambient

 

thermostat switch the unit (heat pumps only) into

(approx 40 to 45 F ambient for 1999 models).

 

defrost (emergency heat) mode?

 

7.

Can the PTAC unit be con®gured to allow continuous

Yes. A switch located on the side of the control

 

fan operation?

box is used to toggle between continuous or cycle

 

 

fan mode.

8.

Can the discharge air grille be changed to alter the

Yes. Remove the 2 screws and ¯ip the grille over

 

direction of the air¯ow?

180 degrees.

9.How does the Emergency Management (EM) accessory In series with the 24-volt control circuit (trans-

kit work?

former is ®eld-supplied) it disconnects the power

 

at the front desk during unoccupied periods. The

 

unit will be energized in emergency heat mode,

 

provided the push button switch is selected for

 

heating, if the room temperature drops below

 

55° F to prevent freezing.

10. When must the accessory subbase be used?

When the wall sleeve is more than 4 in. inside

 

the room. The subbase can be adjusted to a maxi-

 

mum height of 51¤2 inches.

11. How does the PTAC unit prevent condensate water

A temperature-activated drain opens when the

from freezing in the basepan?

temperature drops below 45 F, draining the

 

water into the sleeve to prevent freezing.

12. What does the outdoor thermostat switch do?

The toggle switch, located on the side of the con-

 

trol box, prevents the compressor from energizing

 

in heating mode during subfreezing conditions to

 

ensure adequate heating capacity. The switch

 

must be returned to the ``heat pump'' position for

 

compressor operation during cooling modes.

Copyright 1999 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.

Book

1

4

 

PC 132

Catalog No. 535-227

Printed in U.S.A.

Form 52S-2T

Pg 56

4-99

Replaces: 52S-1T

Tab

9a

11a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 56
Image 56
Carrier 52S manual Most Frequent Ptac Service Questions