MOST FREQUENT PTAC SERVICE QUESTIONS
1. | Can remote thermostats be used on standard (AA) | No, only for use on remote control (RC) models. |
| models? |
|
2. | Which remote thermostats are acceptable for use on | HH01AD045 Ð Manual changeover thermostat |
| 52S products? | TSTATCCPAC01 Ð Programmable AC thermostat |
|
| TSTATCCPHP01 Ð Programmable HP thermostat |
3. | How many 52S series units can be controlled by one | Only 2. |
| remote thermostat? |
|
4. | What is the vent capacity of the 52S products? | 35 cfm (standalone). Capacity can be increased |
|
| with the use of an external exhaust fan. |
5. | How do the 52S series models handle condensate | By using a slinger ring to evaporate the water on |
| removal? | the outdoor coil, and by using an optional acces- |
|
| sory drain kit. |
6. | At what temperature will the outdoor (defrost) | 15 F coil temperature/approx 35 F ambient |
| thermostat switch the unit (heat pumps only) into | (approx 40 to 45 F ambient for 1999 models). |
| defrost (emergency heat) mode? |
|
7. | Can the PTAC unit be con®gured to allow continuous | Yes. A switch located on the side of the control |
| fan operation? | box is used to toggle between continuous or cycle |
|
| fan mode. |
8. | Can the discharge air grille be changed to alter the | Yes. Remove the 2 screws and ¯ip the grille over |
| direction of the air¯ow? | 180 degrees. |
9.How does the Emergency Management (EM) accessory In series with the
kit work? | former is |
| at the front desk during unoccupied periods. The |
| unit will be energized in emergency heat mode, |
| provided the push button switch is selected for |
| heating, if the room temperature drops below |
| 55° F to prevent freezing. |
10. When must the accessory subbase be used? | When the wall sleeve is more than 4 in. inside |
| the room. The subbase can be adjusted to a maxi- |
| mum height of 51¤2 inches. |
11. How does the PTAC unit prevent condensate water | A |
from freezing in the basepan? | temperature drops below 45 F, draining the |
| water into the sleeve to prevent freezing. |
12. What does the outdoor thermostat switch do? | The toggle switch, located on the side of the con- |
| trol box, prevents the compressor from energizing |
| in heating mode during subfreezing conditions to |
| ensure adequate heating capacity. The switch |
| must be returned to the ``heat pump'' position for |
| compressor operation during cooling modes. |