52S
SERIES
| SYMPTOM | COMPRESSOR | COMPRESSOR | COMPRESSOR | COMPRESSOR | COMPRESSOR | |
| STARTS AND | STARTS AFTER | WILL NOT | ||||
| 
 | WILL NOT START | CYCLES OFF | ||||
| 
 | RUNS BUT | CYCLING THE | START. IT HUMS | |||
| POSSIBLE CAUSE | CYCLES ON THE | OVERLOAD | AND CYCLES ON | AND MAKES NO | (NOT ON | |
| 
 | OVERLOAD | SEVERAL TIMES | THE OVERLOAD | NOISE | OVERLOAD) | |
| 
 | 
 | 
 | ||||
| COILS/FILTERS DIRTY OR PLUGGED | X | 
 | 
 | 
 | 
 | |
| AIR OR NONCONDENSABLE GASES | X | X | 
 | 
 | 
 | |
| IN SYSTEM | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | ||
| SYSTEM REFRIGERANT OVERCHARGED | X | 
 | 
 | 
 | X | |
| DISCHARGE LINE RESTRICTED | X | X | 
 | 
 | 
 | |
| CAPILLARY TUBE OR STRAINER | X | X | 
 | 
 | X | |
| RESTRICTED OR PLUGGED | 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | ||
| FAN BLADE OR MOTOR DEFECTIVE | X | 
 | 
 | 
 | X | |
| FAN BLADE OR BLOWER WHEEL STUCK | X | 
 | 
 | 
 | X | |
| SYSTEM REFRIGERANT UNDERCHARGED | X | 
 | 
 | 
 | X | |
| EVAPORATOR AIRFLOW RECIRCULATION | 
 | 
 | 
 | 
 | X | |
| UNIT OVERSIZED FOR APPLICATION | 
 | 
 | 
 | 
 | X | |
| COMPRESSOR REQUIRES START ASSIST | 
 | X | X | 
 | 
 | |
| NO POWER TO UNIT | 
 | 
 | 
 | X | 
 | |
| LOW VOLTAGE TO UNIT | X | X | X | 
 | X | |
| OVERLOAD PROTECTOR OPEN | 
 | 
 | 
 | X | 
 | |
| OVERLOAD PROTECTOR INCORRECT | X | 
 | X | X | 
 | |
| OR DEFECTIVE | 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | ||
| CAPACITOR INCORRECT OR DEFECTIVE | X | X | X | 
 | X | |
| THERMOSTAT CONTACTS ARE OPEN | 
 | 
 | 
 | X | 
 | |
| THERMOSTAT IS SET TOO HIGH OR LOW | 
 | 
 | 
 | X | 
 | |
| SELECTOR SWITCH IS OPEN | 
 | 
 | 
 | X | 
 | |
| OR DEFECTIVE | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | ||
| WIRING IS INCORRECT OR DEFECTIVE | X | 
 | X | X | X | |
| SYSTEM PRESSURES NOT EQUALIZED | 
 | X | X | 
 | X | |
| COMPRESSOR MOTOR OR | X | X | X | X | X | |
| MECHANISM DEFECTIVE | ||||||
| 
 | 
 | 
 | 
 | 
 | ||
| COMPRESSOR GROUNDED | 
 | 
 | X | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
FIGURE 34 Ð BASIC COMPRESSOR TROUBLESHOOTING GUIDE