52S
SERIES
SYMPTOM | COMPRESSOR | COMPRESSOR | COMPRESSOR | COMPRESSOR | COMPRESSOR | |
STARTS AND | STARTS AFTER | WILL NOT | ||||
| WILL NOT START | CYCLES OFF | ||||
| RUNS BUT | CYCLING THE | START. IT HUMS | |||
POSSIBLE CAUSE | CYCLES ON THE | OVERLOAD | AND CYCLES ON | AND MAKES NO | (NOT ON | |
| OVERLOAD | SEVERAL TIMES | THE OVERLOAD | NOISE | OVERLOAD) | |
|
|
| ||||
COILS/FILTERS DIRTY OR PLUGGED | X |
|
|
|
| |
AIR OR NONCONDENSABLE GASES | X | X |
|
|
| |
IN SYSTEM |
|
|
| |||
|
|
|
|
| ||
SYSTEM REFRIGERANT OVERCHARGED | X |
|
|
| X | |
DISCHARGE LINE RESTRICTED | X | X |
|
|
| |
CAPILLARY TUBE OR STRAINER | X | X |
|
| X | |
RESTRICTED OR PLUGGED |
|
| ||||
|
|
|
|
| ||
FAN BLADE OR MOTOR DEFECTIVE | X |
|
|
| X | |
FAN BLADE OR BLOWER WHEEL STUCK | X |
|
|
| X | |
SYSTEM REFRIGERANT UNDERCHARGED | X |
|
|
| X | |
EVAPORATOR AIRFLOW RECIRCULATION |
|
|
|
| X | |
UNIT OVERSIZED FOR APPLICATION |
|
|
|
| X | |
COMPRESSOR REQUIRES START ASSIST |
| X | X |
|
| |
NO POWER TO UNIT |
|
|
| X |
| |
LOW VOLTAGE TO UNIT | X | X | X |
| X | |
OVERLOAD PROTECTOR OPEN |
|
|
| X |
| |
OVERLOAD PROTECTOR INCORRECT | X |
| X | X |
| |
OR DEFECTIVE |
|
| ||||
|
|
|
|
| ||
CAPACITOR INCORRECT OR DEFECTIVE | X | X | X |
| X | |
THERMOSTAT CONTACTS ARE OPEN |
|
|
| X |
| |
THERMOSTAT IS SET TOO HIGH OR LOW |
|
|
| X |
| |
SELECTOR SWITCH IS OPEN |
|
|
| X |
| |
OR DEFECTIVE |
|
|
|
| ||
|
|
|
|
| ||
WIRING IS INCORRECT OR DEFECTIVE | X |
| X | X | X | |
SYSTEM PRESSURES NOT EQUALIZED |
| X | X |
| X | |
COMPRESSOR MOTOR OR | X | X | X | X | X | |
MECHANISM DEFECTIVE | ||||||
|
|
|
|
| ||
COMPRESSOR GROUNDED |
|
| X |
|
| |
|
|
|
|
|
|
FIGURE 34 Ð BASIC COMPRESSOR TROUBLESHOOTING GUIDE