Carrier 69NT20-531-300 manual Safety and Protective Devices

Models: 69NT20-531-300

1 93
Download 93 pages 33.37 Kb
Page 22
Image 22

PARAGRAPH 2.3 -- Continued

 

Orange wire

Power

 

 

 

 

Red wire

Output

 

 

 

 

Brown wire

Ground

 

 

 

 

Input voltage

5 vdc

 

 

 

g. Humidity Sensor

Output voltage

0 to 3.3 vdc

Output voltage readings verses relative humidity (RH) percentage:

 

 

 

 

 

30%

0.99 V

 

 

 

 

50%

1.65 V

 

 

 

 

70%

2.31 V

 

 

 

 

90%

2.97 V

 

 

 

2.4 SAFETY AND PROTECTIVE DEVICES

Unit components are protected from damage by safety and protective devices listed in the following table. These devices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.

Open safety switch contacts on either or both of devices

IP-CP or HPS will shut down the compressor.

Open safety switch contacts on device IP-CM will shut down the condenser fan motor.

The entire refrigeration unit will shut down if one of the following safety devices open: (a) Circuit Breaker(s);

(b)Fuse (F3/15A); or (c) Evaporator Fan Motor Internal Protector(s) - (IP-EM).

Table 2-1 Safety and Protective Devices

UNSAFE CONDITION

DEVICE

DEVICE SETTING

 

 

 

 

Circuit Breaker (CB-1) - Manual Reset

Trips at 29 amps (460 vac)

 

 

 

Excessive current draw

Circuit Breaker (CB-2, 50 amp) -Manual Reset

Trips at 62.5 amps (230 vac)

 

Circuit Breaker (CB-2, 70 amp) -Manual Reset

Trips at 87.5 amps (230 vac)

 

 

 

Excessive current draw in the

Fuse (F3)

10 amp rating

control circuit

 

 

Excessive current draw by the

Fuse (F1 & F2)

5 amp rating

controller

 

 

Excessive current draw by the

Fuse (F4)

10 amp rating

expansion module

 

 

Excessive condenser fan mo-

Internal Protector (IP-CM) - Automatic Reset

N/A

tor winding temperature

 

 

Excessive compressor motor

Internal Protector (IP-CP) - Automatic Reset

N/A

winding temperature

 

 

Excessive evaporator fan mo-

Internal Protector(s) (IP-EM) - Automatic Reset

N/A

tor(s) winding temperature

 

 

Abnormal pressures/tempera-

Fusible Plug - Used on the Receiver

93 _C = (200 _F)

 

 

tures in the high refrigerant

Rupture Disc - Used on the Water-Cooled Con-

35 kg/cm@ = (500 psig)

side

denser

 

 

 

 

 

 

Abnormally high discharge

High Pressure Switch (HPS)

Opens at 25 kg/cm@

pressure

(350 psig)

 

 

 

 

T-309

2-8

Page 22
Image 22
Carrier 69NT20-531-300 manual Safety and Protective Devices