Carrier 69NT20-531-300 manual Controller Function Codes Sheet 3

Models: 69NT20-531-300

1 93
Download 93 pages 33.37 Kb
Page 41
Image 41

 

 

Table 3-5 Controller Function Codes (Sheet 3 of 3)

 

 

 

 

 

 

 

The stagger start offset time is the amount of time that the unit will delay at start-

Cd31

Stagger Start Offset

 

up, thus allowing multiple units to stagger their control initiation when all units

 

Time (Seconds)

 

are powered up together. The eight possible offset values are:

 

 

 

0 (Factory Default), 3, 6, 9, 12, 15, 18 or 21 seconds

 

 

 

 

 

 

 

The current limit is the maximum current draw allowed on any phase at any time.

 

 

 

Limiting the unit’s current reduces the load on the main power supply. This is

Cd32

Current Limit

 

accomplished by reducing the SMV position until current draw is reduced to the

 

(Amperes)

 

set point. When desirable, the limit can be lowered. Note, however, that capacity

 

 

 

is also reduced. The five values for 460vac operation are: 15, 17, 19, 21 (Factory

 

 

 

Default), 23

 

 

 

 

 

 

 

Relative humidity set point is available only on units configured for dehumidifi-

 

 

 

cation. When the mode is activated, the control probe LED flashes on and off ev-

 

 

 

ery second to alert the user. If not configured, the mode is permanently deacti-

 

Perishable Mode

 

vated and ---------- will display. The value can be set to “OFF.” “TEST,” or a

 

 

range of 65 to 95% relative humidity in increments of 1%. [If bulb mode is active

Cd33

Dehumidification

 

 

(code Cd35) and “Lo” speed evaporator motors are selected (code Cd36) then set

 

Control (% RH)

 

 

 

point ranges from 60 to 95%.] When “TEST” is selected or test set point is

 

 

 

 

 

 

entered, the heat LED should illuminate, indicating that dehumidification mode is

 

 

 

activated. After a period of five minutes in the “TEST” mode has elapsed, the

 

 

 

previously selected mode is reinstated.

Cd34

Economy Mode

 

Economy mode is a user selectable mode of operation provided for power saving

 

(On-Off)

 

purposes.

 

 

 

Bulb mode is a user selectable mode of operation that is an extension of dehu-

 

 

 

midification control (Cd33). If dehumidification is set to “Off,” code Cd35 will

Cd35

Bulb Mode

 

display “Nor” and the user will be unable to change it. After a dehumidification

 

set point has been selected and entered for code Cd33, the user may then change

 

 

 

 

 

 

code Cd35 to “bulb.” After bulb has been selected and entered, the user may then

 

 

 

utilize function codes Cd36 and Cd37 to make the desired changes.

 

 

 

 

 

 

 

This code is enabled only if in the dehumidification mode (code Cd33) and bulb

 

 

 

mode (Cd35) has been set to “bulb”. If these conditions are not met, “alt” will be

 

 

 

displayed (indicating that the evaporator fans will alternate their speed) and the

Cd36

Evaporator Speed

 

display cannot be changed. If a dehumidification set point has been selected along

 

Select

 

with bulb mode then “alt” may be selected for alternating speed, “Lo” for low

 

 

 

speed evaporator fan only, or “Hi” for high speed evaporator fan only. If a setting

 

 

 

other than “alt” has been selected and bulb mode is deactivated in any manner,

 

 

 

then selection reverts back to “alt.”

 

 

 

 

 

 

 

This code, as with function code Cd36, is used with bulb mode and dehumidifica-

 

Defrost Termination

 

tion. If bulb mode is active, this code allows the user to change the temperature

Cd37

Temperature Setting

 

defrost will terminate. It allows the user to change the setting within a range of

 

(Bulb Mode)

 

4_C to 25.6_C in 0.1_C (0.2_F) increments. This value is changed using the UP/

 

 

DOWN ARROW keys, followed by the ENTER key when the desired value is

 

 

 

 

 

 

displayed. If bulb mode is deactivated, the DTS setting returns to the default.

 

 

 

 

 

 

 

Display Only Functions - Continued

 

 

 

 

 

 

 

Code Cd38 will display the current secondary supply temperature sensor reading

Cd38

Secondary Supply

 

for units configured for four probes. If the unit is configured with a DataCORD-

Temperature Sensor

 

ER, Cd38 will display ----------.” If the DataCORDER suffers a failure,

 

 

 

(AL55) Cd38 will display the supply recorder sensor reading.

 

 

 

 

 

 

 

Code Cd39 will display the current secondary return temperature sensor reading

Cd39

Secondary Return

 

for units configured for four probes. If the unit is configured with a DataCORD-

Temperature Sensor

 

ER, Cd39 will display ----------.” If the DataCORDER suffers a failure,

 

 

 

(AL55) Cd39 will display the return recorder sensor reading.

 

Container Identifica-

 

Code Cd40 is configured at commissioning to read a valid container identifica-

Cd40

 

tion number. The reading will not display alpha characters, only the numeric por-

 

tion Number

 

tion of the number will display.

 

 

 

 

 

 

 

 

 

 

SERVICE FUNCTION: This code is used for troubleshooting and allows manu-

Cd41

Valve Override

 

al positioning of the economizer, unloader, suction modulation and oil return

 

 

 

valves. Refer to paragraph 6.19 for operating instructions.

 

 

 

 

Cd42

Oil Return Valve

 

The status of the valve is displayed (Open - Closed).

T-309

3-16

Page 41
Image 41
Carrier 69NT20-531-300 manual Controller Function Codes Sheet 3

69NT20-531-300 specifications

The Carrier 69NT20-531-300 is a cutting-edge rooftop unit designed to meet the demanding requirements of commercial heating and cooling applications. This model embodies Carrier’s commitment to energy efficiency, reliability, and advanced technological features that enhance indoor comfort while minimizing operational costs.

One of the standout features of the Carrier 69NT20-531-300 is its high energy efficiency. It is equipped with advanced compressor technology that optimizes performance while reducing energy consumption. This ensures that businesses can maintain a comfortable indoor climate without incurring exorbitant utility bills. With a high Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER), users can expect not only enhanced comfort but also significant cost savings over time.

The cooling capabilities of the 69NT20-531-300 are complemented by its robust heating options. This unit utilizes a gas heat exchanger, ensuring quick and even heating throughout the space. The combination of cooling and heating capabilities in one compact unit makes it a versatile choice for various applications, including retail spaces, offices, and warehouses.

In addition to its impressive performance specifications, the Carrier 69NT20-531-300 incorporates innovative technologies that further enhance its functionality. The unit comes with advanced controls, allowing for precise temperature regulation and zoning capabilities. This ensures that different areas of a building can maintain their desired temperatures based on usage, improving overall energy efficiency.

Durability is another hallmark of the Carrier 69NT20-531-300. The unit is constructed with high-quality materials and features a weather-proof cabinet that protects it from the elements, ensuring long-term reliability even in harsh conditions. Furthermore, its modular design simplifies maintenance, making it easy for technicians to access critical components.

The 69NT20-531-300 is also designed with low noise operation in mind. It employs sound-dampening technology to ensure that operations are quiet, making it an ideal choice for locations where noise reduction is a priority, such as schools or healthcare facilities.

Overall, the Carrier 69NT20-531-300 stands out as a premier choice for businesses looking for an efficient, reliable, and feature-rich rooftop HVAC unit. Its blend of energy efficiency, advanced technology, and durability positions it as a leader in commercial heating and cooling solutions, making it a valuable investment for any commercial property.