| Table | |
|
|
|
|
Code | TITLE |
| DESCRIPTION |
No. |
| ||
|
|
| |
| Note: If the function is not applicable, the display will read | ||
|
|
| Display Only Functions |
|
|
|
|
| Suction Modulation |
| Displays the SMV percent open. The right display reads 100% when the valve is |
Cd01 |
| fully open. The valve will usually be at 10% on start up of the unit except in very | |
| Valve Opening (%) |
| high ambient temperatures. |
|
|
| |
|
|
|
|
Cd02 | Not Applicable |
| Not used |
| Compressor Motor |
| The current sensor measures current draw in lines L1 & L2 by all of the high |
Cd03 |
| voltage components. It also measures current draw in compressor motor leg T3. | |
| Current |
| The compressor leg T3 current is displayed. |
|
|
| |
|
|
|
|
Cd04 | Line Current, |
| The current sensor measures current on two legs. The third unmeasured leg is cal- |
| culated based on a current algorithm. The current measured is used for control | ||
| Phase A |
| |
|
| and diagnostic purposes. For control processing, the highest of the Phase A and B | |
|
|
| |
Cd05 | Line Current, |
| current values is used for current limiting purposes. For diagnostic processing, |
| the current draws are used to monitor component energization.. Whenever a heat- | ||
| Phase B |
| |
|
| er or a motor is turned ON or OFF, the current draw increase/reduction for that | |
|
|
| |
Cd06 | Line Current, |
| activity is measured. The current draw is then tested to determine if it falls within |
| the expected range of values for the component. Failure of this test will result in a | ||
| Phase C |
| |
|
| ||
|
|
| |
|
|
|
|
Cd07 | Main Power Voltage |
| The main supply voltage is displayed. |
|
|
|
|
Cd08 | Main Power Fre- |
| The value of the main power frequency is displayed in Hertz. The frequency dis- |
| quency |
| played will be halved if either fuse F1 or F2 is bad (alarm code AL21). |
Cd09 | Ambient Tempera- |
| The ambient sensor reading is displayed. |
| ture |
|
|
Cd10 | Compressor Suction |
| Compressor suction temperature sensor reading is displayed. |
| Temperature |
|
|
Cd11 | Compressor Dis- |
| Compressor discharge temperature sensor reading is displayed. |
| charge Temperature |
|
|
Cd12 | Compressor Suction |
| Compressor suction pressure transducer reading is displayed. |
| Pressure |
|
|
Cd13 | Not Applicable |
| Not used |
|
|
|
|
Cd14 | Compressor Dis- |
| Compressor discharge pressure transducer reading is displayed. |
| charge Pressure |
|
|
Cd15 | Unloader Valve |
| The status of the valve is displayed (Open - Closed). |
|
|
|
|
Cd16 | Compressor Motor |
| Records total hours of compressor run time. Total hours are recorded in incre- |
| Hour Meter |
| ments of 10 hours (i.e., 3000 hours is displayed as 300). |
Cd17 | Relative Humidity |
| Humidity sensor reading is displayed. This code displays the relative humidity, as |
| (%) |
| a percent value. |
Cd18 | Software Revision # |
| The software revision number is displayed. |
|
|
|
|
|
|
| This code checks the Controller/DataCORDER battery pack. While the test is |
|
|
| running, “btest” will flash on the right display, followed by the result. “PASS” |
|
|
| will be displayed for battery voltages greater than 7.0 volts. “FAIL” will be dis- |
Cd19 | Battery Check |
| played for battery voltages between 4.5 and 7.0 volts, and |
|
|
| displayed for battery voltages less than 4.5 volts. After the result is displayed for |
|
|
| four seconds, “btest” will again be displayed, and the user may continue to scroll |
|
|
| through the various codes. |
Cd20 | Config/Model # |
| This code indicates the dash number of the model for which the Controller is con- |
| figured (i.e., if the unit is a | ||
|
|
| |
Cd21 | Economizer Valve |
| The status of the valve is displayed (Open - Closed). |