![](/images/new-backgrounds/1078633/78633113x1.webp)
FALLING |
TEMPERATURE |
START UNLOADED, |
TRANSITION TO |
ECONOMIZED |
OPERATION |
AIR CIRCULATION |
RISING |
TEMPERATURE |
COOLING |
ECONOMIZED |
+.20_C |
SET POINT |
AIR CIRCULATION |
NOTE: TEMPERATURES INDICATIONS ARE ABOVE OR BELOW SET POINT
Figure 4-3 Controller Operation -- Frozen Mode
ENERGIZED |
| |
CONTROL TRANSFORMER | ||
FOR FULL DIAGRAM AND | ||
| ||
LEGEND, SEE SECTION 7 |
|
POWER TO |
|
|
|
CONTROLLER |
|
|
|
T6 | PB |
| PA |
TD | T6 | PA | PB |
SIGNAL TO |
|
|
|
CONTROLLER | TU | USV |
|
TS |
|
| ESV |
NOTE: HIGH SPEED EVAPORATOR FAN SHOWN. FOR LOW SPEED CONTACT TE IS
Figure 4-4 Perishable Mode
4.9.1Sequence Of operation -- Compressor Phase Sequence
The controller logic will check for proper compressor rotation. If the compressor is rotating in the wrong direction, the controller will energize or
will switch operation from compressor contactor PB to compressor contactor PA. Compressor contactors PA is wired to run the compressor on L1, L2, and L3. Compressor contactor PB is wired to run the compressor on L2, L1 and L3 thus providing reverse rotation .
4.9.2Sequence Of Operation
NOTE
In the Conventional Perishable Mode of opera- tion the evaporator motors run in high speed. In the Economy Perishable Mode the fan speed is varied.
a. With supply air temperature above set point and de- creasing, the unit will be cooling with the condenser fan motor (CF), compressor motor (PA or PB), evap- orator fan motors (EF) energized and the COOL light illuminated. (See Figure
b. When the air temperature decreases to a predeter- mined tolerance above set point, the
c. As the air temperature continues to fall, modulating cooling starts at approximately 2.5_C (4.5_F) above set point. (See Figure