Table 5B — Part Load Data Percent Displacement, with Accessory Unloaders (cont)

UNIT

CONTROL

LOADING SEQUENCE A

LOADING SEQUENCE B

30GTN,R

STEPS

% Displacement

Compressors

% Displacement

Compressors

30GUN,R

(Approx)

(Approx)

 

 

 

 

1

8

A1†

8

B1†

 

2

14

A1*

14

B1*

 

3

21

A1

21

B1

 

4

22

A1†,B1*

22

A1*,B1†

 

5

28

A1†,B1

28

A1,B1†

 

6

35

A1*,B1

35

A1,B1*

 

7

42

A1,B1

42

A1,B1

130 (60 Hz)

8

44

A1†,A2,B1†

44

A1†,B1†,B2

9

51

A1†,A2,B1*

51

A1*,B1†,B2

 

10

58

A1†,A2,B1

58

A1,B1†,B2

 

11

64

A1,A2,B1

64

A1,B1*,B2

 

12

71

A1,A2,B1†

71

A1,B1,B2

 

13

73

A1†,A2,B1†,B2

73

A1†,A2,B1†,B2

 

14

80

A1†,A2,B1*,B2

80

A1*,A2,B1†,B2

 

15

87

A1†,A2,B1,B2

87

A1,A2,B1†,B2

 

16

93

A1*,A2,B1,B2

93

A1,A2,B1*,B2

 

17

100

A1,A2,B1,B2

100

A1,A2,B1,B2

 

1

6

A1†

8

B1†

 

2

10

A1*

16

B1*

 

3

14

A1

25

B1

 

4

22

A1†,B1*

31

A1,B1*

 

5

31

A1†,B1

39

A1,B1

 

6

35

A1*,B1

43

A1*,B1†,B2

 

7

39

A1,B1

47

A1,B1†,B2

 

8

40

A1†,A2,B1*

56

A1,B1*,B2

130 (50 Hz)

9

49

A1†,A2,B1

64

A1,B1,B2

10

53

A1*,A2,B1

65

A1,A2,B1†,B2

 

11

57

A1,A2,B1

74

A1,A2,B1*,B2

 

12

65

A1†,A2,B1*,B2

82

A1,A2,B1,B2

 

13

74

A1†,A2,B1,B2

83

A1,A2,A3,B1†,B2

 

14

78

A1*,A2,B1,B2

91

A1,A2,A3,B1*,B2

 

15

82

A1,A2,B1,B2

100

A1,A2,A3,B1,B2

 

16

83

A1†,A2,A3,B1*,B2

 

17

91

A1†,A2,A3,B1,B2

 

18

96

A1*,A2,A3,B1,B2

 

19

100

A1,A2,A3,B1,B2

 

1

6

A1†

9

B1†

 

2

11

A1*

18

B1*

 

3

15

A1

27

B1

 

4

24

A1†,B1*

33

A1,B1*

 

5

33

A1†,B1

42

A1,B1

 

6

38

A1*,B1

46

A1*,B1†,B2

 

7

42

A1,B1

51

A1,B1†,B2

150, 230A, 245A,

8

49

A1†,A2,B1

60

A1,B1*,B2

9

53

A1*,A2,B1

69

A1,B1,B2

255A (60 Hz)

10

58

A1,A2,B1

75

A1,A2,B1*,B2

 

 

11

66

A1†,A2,B1*,B2

86

A1,A2,B1,B2

 

12

75

A1†,A2,B1,B2

91

A1,A2,A3,B1*,B2

 

13

80

A1*,A2,B1,B2

100

A1,A2,A3,B1,B2

 

14

85

A1,A2,B1,B2

 

15

91

A1†,A2,A3,B1,B2

 

16

95

A1*,A2,A3,B1,B2

 

17

100

A1,A2,A3,B1,B2

 

1

6

A1†

6

B1†

 

2

13

A1*

13

B1*

 

3

20

A1

20

B1

 

4

26

A1†,B1

26

A1,B1†

 

5

33

A1*,B1

33

A1,B1*

 

6

40

A1,B1

40

A1,B1

150, 230A, 245A,

7

46

A1†,A2,B1

46

A1,B1†,B2

8

53

A1*,A2,B1

53

A1,B1*,B2

255A (50 Hz)

9

60

A1,A2,B1

60

A1,B1,B2

 

 

10

66

A1†,A2,B1,B2

66

A1,A2,B1†,B2

 

11

73

A1*,A2,B1,B2

73

A1,A2,B1*,B2

 

12

80

A1,A2,B1,B2

80

A1,A2,B1,B2

 

13

86

A1†,A2,A3,B1,B2

86

A1,A2,A3,B1†,B2

 

14

93

A1*,A2,A3,B1,B2

93

A1,A2,A3,B1*,B2

 

15

100

A1,A2,A3,B1,B2

100

A1,A2,A3,B1,B2

*Unloaded compressor.

Two unloaders, both unloaded.

NOTE: These capacity control steps may vary due to lag compressor sequencing.

23