Carrier Air Conditioner specifications Appendix A - Ccn Tables, UNIT Configuration Settings

Models: Air Conditioner

1 96
Download 96 pages 57.36 Kb
Page 71
Image 71

APPENDIX A — CCN TABLES

UNIT (Configuration Settings)

 

DESCRIPTION

 

STATUS

DEFAULT

UNITS

POINT

1

Unit Type

1

= Air Cooled

1

 

UNIT_TYP

 

 

2

= Water Cooled

 

 

 

 

 

3

= Split System

 

 

 

 

 

4

= Heat Machine

 

 

 

 

 

5

= Air Cooled Heat Reclaim

 

 

 

 

 

 

 

 

 

2

Unit Size

20 to 300

*

TONS

SIZE

3

Circuit A1% Capacity

0 to 100

*

%

CAP_A

4

Number Circ A Compressor

1 to 4

*

 

NUMCA

5

Compressor A1 Cylinders

4 or 6

*

 

NUM_CYLA

6

Number Circ B Compressor

1 to 4

*

 

NUMCB

7

Compressor B1 Cylinders

4 or 6

*

 

NUM_CYLB

8

EXV Module Installed

No/Yes

Yes

 

EXV_BRD

9

EXV Superheat Setpoint

10 to 40

29.0 (30GTN,R)

^F

SH_SP

 

 

 

 

23.0 (30GUN,R)

 

 

 

 

 

 

 

 

10

EXV MOP

40 to 80

50.0

°F

MOP_SP

11

EXV Superheat Offset

–20 to 20

0.0

^F

SH_OFFST

12

EXV Circ. A Min Position

0 to 100

8.0

%

EXVAMINP

13

EXV Circ. B Min Position

0 to 100

8.0

%

EXVBMINP

14

Refrigerant

1

= R22

1 (30GTN,R)

 

REFRIG_T

 

 

2

= R134A

2 (30GUN,R)

 

 

 

 

 

 

 

 

15

Low Pressure Setpoint

3 to 60

10.0

PSI

LOW_PRES

16

Fan Staging Select

1

= 2 Stage indpt.

*

 

FAN_TYPE

 

 

2

= 3 Stage indpt.

 

 

 

 

 

3

= 2 Stage common

 

 

 

 

 

4

= 3 Stage common

 

 

 

OPTIONS1 (Options Configuration)

 

DESCRIPTION

 

STATUS

DEFAULT

POINT

1

Cooler Fluid

1

= Water

1

FLUIDTYP

 

 

2

= Med. Brine

 

 

 

 

3

= Low Brine

 

 

2

Hot Gas Bypass Select

No/Yes

No

HGBV_FLG

3

Head Press. Cont. Method

1

= EXV controlled

2

HEAD_MET

 

 

2

= Setpoint control

 

 

 

 

3

= Setpoint-A, EXV-B

 

 

 

 

4

= EXV-A, Setpoint-B

 

 

 

 

 

 

 

 

4

Head Press. Control Type

0

= None

1

HEAD_TYP

 

 

1

= Air Cooled

 

 

 

 

2

= Water Cooled

 

 

 

 

 

 

 

5

Motormaster Select

No/Yes

No

MTR_TYPE

6

Pressure Transducers

Off/On

Off

PRESS_TY

8

Cooler Pump Control

Off/On

Off

CPC

9

Condenser Pump Interlock

Off/On

Off

CND_LOCK

10

Condenser Pump Control

0

= No control

0

CNPC

 

 

1

= On with Mode

 

 

 

 

2

= On with Compressors

 

 

11

Condenser Fluid Sensors

No/Yes

No

CD_TEMP

12

No. Circuit A Unloaders

0-2

*

NUNLA

13

No. Circuit B Unloaders

0-2

*

NUNLB

14

EMM Module Installed

No/Yes

No

EMM_BRD

*Unit size dependent.

71

Page 71
Image 71
Carrier Air Conditioner specifications Appendix A - Ccn Tables, UNIT Configuration Settings, OPTIONS1 Options Configuration