Table 29 — Alarm and Alert Codes

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

T051

Alert

Circuit A, Compressor 1

Compressor feedback signal

Circuit A shut down.

Manual

High-pressure or loss-of-

 

 

Failure

does not match relay state

 

 

charge switch open, faulty

 

 

 

 

 

 

control relay or CPCS board,

 

 

 

 

 

 

loss of condenser air, liquid

 

 

 

 

 

 

valve closed, operation

 

 

 

 

 

 

beyond capability.

T052

Alert

Circuit A, Compressor 2

Compressor feedback signal

Circuit A shut down. Circuit

Manual

High-pressure switch open,

 

 

Failure

does not match relay state

restarted in 1 minute. Com-

 

faulty control relay or CPCS

 

 

 

 

pressor A2 not used until

 

board, loss of condenser air,

 

 

 

 

alarm is reset.

 

liquid valve closed, opera-

 

 

 

 

 

 

tion beyond capability.

T053

Alert

Circuit A, Compressor 3

Compressor feedback signal

Circuit A shut down. Circuit

Manual

High-pressure switch open,

 

 

Failure

does not match relay state

restarted in 1 minute. Com-

 

faulty control relay or CPCS

 

 

 

 

pressor A3 not used until

 

board, loss of condenser air,

 

 

 

 

alarm is reset.

 

liquid valve closed, opera-

 

 

 

 

 

 

tion beyond capability.

T054

Alert

Circuit A, Compressor 4

Compressor feedback signal

Circuit A shut down. Circuit

Manual

High-pressure switch open,

 

 

Failure

does not match relay state

restarted in 1 minute. Com-

 

faulty control relay or CPCS

 

 

 

 

pressor A4 not used until

 

board, loss of condenser air,

 

 

 

 

alarm is reset.

 

liquid valve closed, opera-

 

 

 

 

 

 

tion beyond capability.

T055

Alert

Circuit B, Compressor 1

Compressor feedback signal

Circuit B shut down.

Manual

High-pressure or loss-of-

 

 

Failure

does not match relay state

 

 

charge switch open, faulty

 

 

 

 

 

 

control relay or CPCS board,

 

 

 

 

 

 

loss of condenser air, liquid

 

 

 

 

 

 

valve closed, operation

 

 

 

 

 

 

beyond capability.

T056

Alert

Circuit B, Compressor 2

Compressor feedback signal

Circuit B shut down. Circuit

Manual

High-pressure switch open,

 

 

Failure

does not match relay state

restarted in 1 minute. Com-

 

faulty control relay or CPCS

 

 

 

 

pressor B2 not used until

 

board, loss of condenser air,

 

 

 

 

alarm is reset.

 

liquid valve closed, opera-

 

 

 

 

 

 

tion beyond capability.

T057

Alert

Circuit B, Compressor 3

Compressor feedback signal

Circuit B shut down. Circuit

Manual

High-pressure switch open,

 

 

Failure

does not match relay state

restarted in 1 minute. Com-

 

faulty control relay or CPCS

 

 

 

 

pressor B3 not used until

 

board, loss of condenser air,

 

 

 

 

alarm is reset.

 

liquid valve closed, opera-

 

 

 

 

 

 

tion beyond capability.

A060

Alarm

Cooler Leaving Fluid

Thermistor outside range of

Chiller shutdown after

Automatic

Thermistor failure, damaged

 

 

Thermistor Failure (T1)

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

A061

Alarm

Cooler Entering Fluid

Thermistor outside range of

Chiller shutdown after

Automatic

Thermistor failure, damaged

 

 

Thermistor Failure (T2)

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

T064

Alert

Circuit A Saturated Con-

Thermistor outside range of

Circuit A shutdown after

Automatic

Thermistor failure, damaged

 

 

densing Thermistor Failure

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

 

 

(T3)

 

 

 

 

T065

Alert

Circuit B Saturated Con-

Thermistor outside range of

Circuit B shutdown after

Automatic

Thermistor failure, damaged

 

 

densing Thermistor Failure

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

 

 

(T4)

 

 

 

 

T066

Alert

Circuit A Saturated Suction

Thermistor outside range of

Circuit A shutdown after

Automatic

Thermistor failure, damaged

 

 

Thermistor Failure (T5)

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

 

 

 

 

(EXV only)

 

 

T067

Alert

Circuit B Saturated Suction

Thermistor outside range of

Circuit B shutdown after

Automatic

Thermistor failure, damaged

 

 

Thermistor Failure (T6)

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

 

 

 

 

(EXV only).

 

 

T068

Alert

Compressor A1 Suction

Thermistor outside range of

Circuit A shutdown after

Automatic

Thermistor failure, damaged

 

 

Gas Thermistor Failure (T7)

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

 

 

 

 

(EXV only).

 

 

T069

Alert

Compressor B1 Suction

Thermistor outside range of

Circuit B shutdown after

Automatic

Thermistor failure, damaged

 

 

Gas Thermistor Failure (T8)

–40 to 245 F (–40 to 118 C)

pumpdown complete.

 

cable/wire or wiring error.

 

 

 

 

(EXV only).

 

 

 

 

 

 

 

 

 

T073

Alert

Outside Air Thermistor

Thermistor outside range of

Temperature reset disabled.

Automatic

Thermistor failure, damaged

 

 

Failure (T9)

–40 to 245 F (–40 to 118 C)

Chiller runs under normal

 

cable/wire or wiring error.

 

 

 

 

control/set points.

 

 

T074

Alert

Space Temperature

Thermistor outside range of

Temperature reset disabled.

Automatic

Thermistor failure, damaged

 

 

Thermistor Failure (T10)

–40 to 245 F (–40 to 118 C)

Chiller runs under normal

 

cable/wire or wiring error.

 

 

 

 

control/set points.

 

 

 

 

 

 

 

 

 

T077

Alert

Circuit A Saturated

Saturated suction is

Circuit A shutdown after

Automatic

Faulty expansion valve or

 

 

Suction Temperature

greater than leaving fluid

pumpdown complete.

 

EXV board, faulty cooler suc-

 

 

exceeds Cooler Leaving

temperature for more than

 

 

tion thermistor (T5) or leav-

 

 

Fluid Temperature

5 minutes

 

 

ing fluid thermistor (T1).

T078

Alert

Circuit B Saturated

Saturated suction is

Circuit B shutdown after

Automatic

Faulty expansion valve or

 

 

Suction Temperature

greater than leaving fluid

pumpdown complete

 

EXV board, faulty cooler suc-

 

 

exceeds Cooler Leaving

temperature for more than

 

 

tion thermistor (T6) or leav-

 

 

Fluid Temperature

5 minutes

 

 

ing fluid thermistor (T1).

T079

Alert

Lead/Lag Thermistor Failure

Thermistor outside range of

Lead/lag algorithm runs

Automatic

Dual chiller LWT thermistor

 

 

 

–40 to 245 F (–40 to 118 C)

using Master LWT sensor

 

failure, damaged cable/wire

 

 

 

 

Master is lead chiller.

 

or wiring error.

49

Page 49
Image 49
Carrier Air Conditioner specifications Alarm and Alert Codes, T051

Air Conditioner specifications

Carrier Air Conditioners have long been synonymous with reliability and innovation in climate control. Founded by Willis Carrier, the inventor of modern air conditioning, the brand has continuously set industry standards through state-of-the-art technologies and features designed to enhance indoor comfort.

One of the standout features of Carrier air conditioners is their energy efficiency. Many models are equipped with advanced inverter technology, allowing the compressor to adjust its speed based on the cooling demand. This results in decreased energy consumption, which not only reduces utility bills but also lessens the environmental impact. Recognizing the importance of sustainable practices, Carrier has integrated eco-friendly refrigerants into their systems, further promoting energy-efficient operations.

Carrier also emphasizes user comfort through its variable speed systems. These systems maintain consistent temperatures while minimizing temperature fluctuations, ensuring an even distribution of cool air throughout the home. Additionally, many Carrier models come with advanced air filtration systems, designed to capture allergens, dust, and other particulates, thereby improving indoor air quality.

The smart technology featured in Carrier air conditioners plays a key role in modern convenience. Many units are compatible with smart home systems, allowing users to control settings remotely via smartphones or voice-activated devices. With features like programmable thermostats, users can easily set cooling schedules to match their lifestyle, ensuring comfort while maximizing energy savings.

Durability and noise reduction are also central to the Carrier brand. Many models are designed with sound-dampening features, making them some of the quietest units on the market. This is particularly advantageous for residential use, where noise can disrupt daily activities and sleep.

In terms of design, Carrier air conditioners come in various styles and capacities to suit a wide range of spaces, from compact apartment units to large central systems for sprawling homes. Their extensive warranty and service offerings further reinforce Carrier’s commitment to customer satisfaction.

In conclusion, Carrier air conditioners represent a perfect blend of cutting-edge technology, energy efficiency, and user comfort. Their emphasis on sustainability and smart features positions them as a leading choice for homeowners seeking reliable and innovative climate control solutions. Whether for cooling a small room or an entire house, Carrier remains a trusted name in air conditioning.