Table 29 — Alarm and Alert Codes (cont)
ALARM/ | ALARM |
| WHY WAS THIS | ACTION TAKEN | RES | PROBABLE | |
ALERT | OR | DESCRIPTION | ALARM | ||||
BY CONTROL | METHOD | CAUSE | |||||
CODE | ALERT |
| GENERATED? | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
T203 | Alert | Loss of Communica- | Master MBB loses | Dual chiller control dis- | Automatic | Wiring error, faulty wir- | |
|
| tion with Slave Chiller | communication with | abled. Chiller runs as a |
| ing, failed Slave MBB | |
|
|
| Slave MBB |
| module, power loss at | ||
|
|
|
|
|
| Slave chiller, wrong | |
|
|
|
|
|
| slave address. | |
T204 | Alert | Loss of Communica- | Slave MBB loses com- | Dual chiller control dis- | Automatic | Wiring error, faulty wir- | |
|
| tion with Master Chiller | munication with Master | abled. Chiller runs as a |
| ing, failed Master MBB | |
|
|
| MBB |
| module, power loss at | ||
|
|
|
|
|
| Master chiller. | |
T205 | Alert | Master and Slave | Master and slave chiller | Dual chiller routine dis- | Automatic | CCN Address for both- | |
|
| Chiller with Same | have the same CCN | abled. Master/slave run |
| chillers is the same. | |
|
| Address | address (CCN.A) | as |
| Must be different. | |
|
|
|
|
|
| Check CCN.A under | |
|
|
|
|
|
| the OPT2 | |
|
|
|
|
|
| configuration at both | |
|
|
|
|
|
| chillers. | |
|
|
|
|
|
|
| |
T206 | Alert | High Leaving Chilled | LWT read is greater | Alert only. No action | Automatic | Building load greater | |
|
| Water Temperature | than LCW Alert Limit, | taken. |
| than unit capacity, low | |
|
|
| plus control point and |
|
| water/brine flow or | |
|
|
| Total capacity is 100% |
|
| compressor fault. | |
|
|
| and LWT is greater |
|
| Check for other | |
|
|
| than LWT reading one |
|
| alarms/alerts. | |
|
|
| minute ago |
|
|
| |
A207 | Alarm | Cooler Freeze | Cooler EWT or LWT is | Chiller shutdown with- | Automatic for | Faulty thermistor (T1/ | |
|
| Protection | less than freeze* | out going through | first occurrence | T2), low water flow. | |
|
|
|
| pumpdown. Cooler | of day. Manual |
| |
|
|
|
| pump continues to run | reset thereafter. |
| |
|
|
|
| (if control enabled). |
|
| |
A208 | Alarm | Low Cooler Fluid Flow | Cooler EWT is less | Chiller shutdown with- | Manual | Faulty cooler pump, | |
|
|
| than LWT by 3° F | out going through |
| low water flow, plugged | |
|
|
| (1.7° C) for 1 minute | pumpdown. Cooler |
| fluid strainer. | |
|
|
| after a circuit is started | pump shut off (if control |
|
| |
|
|
|
| enabled). |
|
| |
|
|
|
|
|
|
| |
T950 | Alert | Loss of Communica- | No communications | WSM forces removed. | Automatic | Failed module, wiring | |
|
| tion with WSM | have been received by | Chiller runs under own |
| error, failed trans- | |
|
|
| MBB within 5 minutes | control. |
| former, loose connec- | |
|
|
| of last transmission |
|
| tion plug, wrong | |
|
|
|
|
|
| address. | |
T951 | Alert | Loss of Communica- | No communications | FSM forces removed. | Automatic | Failed module, wiring | |
|
| tion with FSM | have been received by | Chiller runs under own |
| error, failed trans- | |
|
|
| MBB within 5 minutes | control. |
| former, loose connec- | |
|
|
| of last transmission |
|
| tion plug, wrong | |
|
|
|
|
|
| address. |
| LEGEND |
CCN | — Carrier Comfort Network |
CPCS — Compressor Protection Control System | |
CXB | — Compressor Expansion Board |
EMM | — Energy Management Module |
EXV | — Electronic Expansion Valve |
FSM | — Flotronic™ System Manager |
LCW | — Leaving Chilled Water |
LWT | — Leaving Fluid Temperature |
MBB | — Main Base Board |
MOP | — Maximum Operating Pressure |
WSM | — Water System Manager |
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze is CSP.1
NOTE: The following table shows illegal configurations:
1Unit type = 0.
24 Compressors in a circuit with 2 unloaders.
34 Compressors in a circuit with 1 unloader and hot gas bypass.
42 Unloaders and hot gas bypass in a circuit.
5More than one compressor difference between circuits (e.g., 4 compressors in Ckt A, 2 in Ckt B).
6Water cooled units with optional thermistors and configured for head pressure control.
7Split system chillers with optional thermistors and configured for head pressure control.
8Low temperature brine selected for air cooled chillers or split systems with air cooled head pressure control.
9Water cooled unit configured for air cooled head pressure control.
Air cooled head pressure control with common fan staging
10and different head pressure control methods for each circuit (EXV controlled vs. set point controlled).
11Lead/lag enabled, Master selected and Cooling Set Point select is LWT POT.
12Water cooled or split units (units types 2, 3, 4) with more than one compressor on a circuit.
13Condenser pump interlock enabled on air cooled unit.
14Unit type changed.
15Low pressure set points out of range.
16Cooler fluid type is water and ice mode is enabled.
52