ALARM/ | ALARM |
| WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE | |
ALERT | OR | DESCRIPTION | ALARM | ||||
BY CONTROL | METHOD | CAUSE | |||||
CODE | ALERT |
| GENERATED? | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
T112 | Alert | Circuit A High Suction | If EXV is greater than | Circuit A shutdown after | Manual | Faulty expansion | |
|
| Superheat | 98%, suction superheat is | pumpdown complete. |
| valve or EXV board, | |
|
|
| greater than 75 F (41.7 C) |
|
| low refrigerant | |
|
|
| and saturated suction |
|
| charge, plugged fil- | |
|
|
| temperature is less than |
|
| ter drier, faulty suc- | |
|
|
| MOP for 5 minutes |
|
| tion gas thermistor | |
|
|
|
|
|
| (T7) or cooler ther- | |
|
|
|
|
|
| mistor (T5). | |
T113 | Alert | Circuit B High Suction | If EXV is greater than | Circuit B shutdown after | Manual | Faulty expansion | |
|
| Superheat | 98% suction superheat is | pumpdown complete. |
| valve or EXV board, | |
|
|
| greater than 75 F (41.7 C) |
|
| low refrigerant | |
|
|
| and saturated suction |
|
| charge, plugged fil- | |
|
|
| temperature is less than |
|
| ter drier, faulty suc- | |
|
|
| MOP for 5 minutes |
|
| tion gas thermistor | |
|
|
|
|
|
| (T8) or cooler ther- | |
|
|
|
|
|
| mistor (T6). | |
T114 | Alert | Circuit A Low Suction | If EXV is greater than | Circuit A shutdown after | Automatic restart | Faulty expansion | |
|
| Superheat | 10%, and either suction | pumpdown complete. | after first daily | valve or EXV board, | |
|
|
| superheat is less than |
| occurrence. | faulty suction gas | |
|
|
| superheat set point |
| Manual restart | thermistor (T7) or | |
|
|
| (5.6 C) or saturated |
| thereafter. | cooler thermistor | |
|
|
| suction temperature is |
|
| (T5). | |
|
|
| greater than MOP for |
|
|
| |
|
|
| 5 minutes |
|
|
| |
T115 | Alert | Circuit B Low Suction | If EXV is greater than | Circuit B shutdown after | Automatic restart | Faulty expansion | |
|
| Superheat | 10%, and either suction | pumpdown complete. | after first daily | valve or EXV board, | |
|
|
| superheat is less than |
| occurrence. | faulty suction gas | |
|
|
| superheat set point |
| Manual restart | thermistor (T8) or | |
|
|
| (5.6 C) or saturated |
| thereafter. | cooler thermistor | |
|
|
| suction temperature is |
|
| (T6). | |
|
|
| greater than MOP for |
|
|
| |
|
|
| 5 minutes |
|
|
| |
T116 | Alert | Circuit A Low Cooler | 1. If the saturated suction | 1. Mode 7 initiated. No addi- | 1. Automatic reset | Faulty expansion | |
|
| Suction Temperature | temperature is 24 to | tional capacity increases. | if corrected. | valve or EXV board, | |
|
|
| 29° F (13.3 to 16.1° C) | Alert not tripped. |
| low refrigerant | |
|
|
| below cooler LWT and |
|
| charge, plugged fil- | |
|
|
| is also 2° F (1.1° C) |
|
| ter drier, faulty suc- | |
|
|
| less than freeze* |
|
| tion gas thermistor | |
|
|
| 2. If the saturated suction | 2. Circuit shutdown without | 2. Manual | (T7) or cooler ther- | |
|
|
| temperature is 30° F | going through pumpdown. |
| mistor (T5), low | |
|
|
| (16.7° C) below cooler |
|
| cooler fluid flow. | |
|
|
| LWT and is also 2° F |
|
|
| |
|
|
| (1.1° C) less than |
|
|
| |
|
|
| freeze* for 10 minutes |
|
|
| |
T117 | Alert | Circuit B Low Cooler | 1. If the saturated suction | 1. Mode 8 initiated. No addi- | 1. Automatic reset | Faulty expansion | |
|
| Suction Temperature | temperature is 24 to | tional capacity increases. | if corrected. | valve or EXV board, | |
|
|
| 29°F (13.3 to 16.1° C) | Alert not tripped. |
| low refrigerant | |
|
|
| below cooler LWT and |
|
| charge, plugged fil- | |
|
|
| is also 2°F (1.1° C) |
|
| ter drier, faulty suc- | |
|
|
| less than freeze* |
|
| tion gas thermistor | |
|
|
| 2. If the saturated suction | 2. Circuit shutdown without | 2. Manual | (T8) or cooler ther- | |
|
|
| temperature is 30° F | going through pumpdown. |
| mistor (T6), low | |
|
|
| (16.7° C) below cooler |
|
| cooler fluid flow. | |
|
|
| LWT and is also 2° F |
|
|
| |
|
|
| (1.1° C) less than |
|
|
| |
|
|
| freeze* for 10 minutes |
|
|
| |
T118 | Alert | Circuit A Low Oil | Oil pressure switch open | Circuit shutdown without | Manual | Oil pump failure, low | |
|
| Pressure | after 1 minute of continu- | going through pumpdown. |
| oil level, switch fail- | |
|
|
| ous operation |
|
| ure or compressor | |
|
|
|
|
|
| circuit breaker | |
|
|
|
|
|
| tripped. | |
T119 | Alert | Circuit B Low Oil | Oil pressure switch open | Circuit shutdown without | Manual | Oil pump failure, low | |
|
| Pressure | after 1 minute of continu- | going through pumpdown. |
| oil level, switch fail- | |
|
|
| ous operation |
|
| ure or compressor | |
|
|
|
|
|
| circuit breaker | |
|
|
|
|
|
| tripped. | |
|
|
|
|
|
|
|
| LEGEND |
CCN | — Carrier Comfort Network |
CPCS — Compressor Protection Control System | |
CXB | — Compressor Expansion Board |
EMM | — Energy Management Module |
EWT | — Entering Fluid Temperature |
EXV | — Electronic Expansion Valve |
FSM | — Flotronic™ System Manager |
LCW | — Leaving Chilled Water |
LWT | — Leaving Fluid Temperature |
MBB | — Main Base Board |
MOP | — Maximum Operating Pressure |
WSM | — Water System Manager |
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze is CSP.1
50