Carrier Air Conditioner A - Example of Configuring Dual Chiller Control, Master Chiller

Models: Air Conditioner

1 96
Download 96 pages 57.36 Kb
Page 39
Image 39

Table 18A — Example of Configuring Dual Chiller Control

(Master Chiller)

SUB-MODE

KEYPAD ENTRY

ITEM

DISPLAY

ITEM EXPANSION

COMMENT

RSET

ENTER

CRST

0

COOLING RESET TYPE

 

 

 

 

 

LLDY

5

LAG START DELAY

 

 

ENTER

 

5

 

Scrolling stops

 

 

 

 

 

ENTER

 

5

 

Value flashes

 

 

 

 

 

 

 

10

 

Select 10

 

ENTER

 

10

 

Change accepted

 

 

 

 

 

ESCAPE

LLDY

10

 

 

 

 

LLBD

168

LEAD/LAG BALANCE DELTA

No change needed. Default set for weekly changeover

 

 

LLBL

DSBL

LEAD/LAG BALANCE SELECT

 

 

ENTER

 

DSBL

 

Scrolling stops

 

 

 

 

 

ENTER

 

DSBL

 

Value flashes

 

 

 

 

 

 

 

ENBL

 

Select Enable

 

ENTER

 

ENBL

 

Change accepted

 

 

 

 

 

ESCAPE

LLBL

ENBL

 

 

 

 

 

 

 

 

SLVA

0

SLAVE ADDRESS

 

 

ENTER

 

0

 

Scrolling stops

 

 

 

 

 

ENTER

 

0

 

Value flashes

 

 

 

 

 

 

 

6

 

Select 6

 

ENTER

 

6

 

Change accepted

 

 

 

 

 

ESCAPE

SLVA

6

 

 

 

 

MSSL

MAST

MASTER/SLAVE SELECT

No change needed. Default set for Master

Table 18B — Example of Configuring Dual Chiller Control

(Slave Chiller)

SUB-MODE

KEYPAD ENTRY

ITEM

DISPLAY

ITEM EXPANSION

COMMENT

RSET

ENTER

CRST

0

COOLING RESET TYPE

 

 

 

 

 

LLDY

5

LAG START DELAY

 

 

 

LLBD

168

LEAD/LAG BALANCE DELTA

No change needed. Default set for weekly changeover

 

 

LLBL

DSBL

LEAD/LAG BALANCE SELECT

 

 

 

SLVA

0

SLAVE ADDRESS

 

 

 

MSSL

MAST

MASTER/SLAVE SELECT

Default set for Master

 

ENTER

MAST

 

 

Scrolling stops

 

 

 

 

 

ENTER

MAST

 

 

Value flashes

 

 

 

 

 

 

SLVE

 

 

Select SLVE

 

ENTER

SLVE

 

 

Change accepted

 

 

 

 

 

 

MSSL

 

 

Item/Value/Units scrolls again

 

 

LLEN

DSBL

LEAD/LAG CHILLER ENABLE

 

 

ENTER

 

DSBL

 

Scrolling stops

 

 

 

 

 

ENTER

 

DSBL

 

Value flashes

 

 

 

 

 

 

 

ENBL

 

Select enable

 

ENTER

LLEN

ENBL

 

Change accepted

 

 

 

 

ESCAPE

LLEN

ENBL

LEAD/LAG CHILLER ENABLE

Item/Value/Units scrolls again

 

 

 

 

39

 

Page 39
Image 39
Carrier Air Conditioner specifications A - Example of Configuring Dual Chiller Control, Master Chiller