Table 16 — Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ITEM

MARQUEE

NAVIGATOR

ITEM EXPANSION

COMMENT

ENTRY

DISPLAY RANGE

DISPLAY RANGE

 

 

 

 

OPT2

 

BAUD

1 - 5

2400

CCN BAUD RATE

Default: 3

 

4800

(cont)

 

 

 

 

1 = 2400

 

 

 

 

9600

 

2 = 4800

 

 

 

 

19,200

 

3 = 9600

 

 

 

 

38,400

 

4 = 19,200

 

 

 

 

 

 

5 = 38,400

 

 

 

 

EQUAL

LOADING SEQUENCE

Default: 1

 

 

LOAD

1 - 2

1 = Equal

 

 

STAGED

SELECT

 

 

 

 

2 = Staged

 

 

 

 

 

 

 

 

LLCS

1 - 3

AUTOMATIC

LEAD/LAG CIRCUIT

Default: 1 (Size 080-420);

 

 

 

 

CIR A LEADS

SELECT

2 (Size 040-070)

 

 

 

 

CIR B LEADS

 

1 = Automatic

 

 

 

 

 

 

2 = Circuit A Leads

 

 

 

 

 

 

3 = Circuit B Leads

 

 

LCWT

2 - 60 F

2 - 60 F

HIGH LCW ALERT

Default: 60

 

 

(–16 - 16 C)

(–16 - 16 C)

LIMIT

 

 

 

 

 

 

DELY

0 - 15

0 - 15

MINUTES OFF TIME

Default: 0

 

 

ICE.M

ENBL-DSBL

ENBL-DSBL

ICE MODE ENABLE

Default: DSBL

RSET

 

 

 

NO RESET

 

0 = No report

 

 

 

 

 

 

 

 

 

4-20 INPUT

 

 

 

 

 

COOLING RESET

2 = 4 to 20 mA input

 

ENTER

CRST

0 - 4

OUT AIR TEMP

 

TYPE

3 = Return fluid

 

 

 

 

RETURN FLUID

 

 

 

 

 

4 = Space temperature

 

 

 

 

SPACE TEMP

 

 

 

 

 

 

 

 

 

CRT1

0° - 125 F

0° - 125 F

NO COOL RESET

Default: 125 F

 

 

(–18 - 52 C)

(–18 - 52 C)

TEMP

 

 

 

 

 

 

CRT2

0° - 125 F

0° - 125 F

FULL COOL RESET

Default: 0° F

 

 

(–18 - 52 C)

(–18 - 52 C)

TEMP

 

 

 

 

 

 

DGRC

–30 - 30 F

–30 - 30 F

DEGREES COOL

Default: 0° F

 

 

(–17 - 17 C)

(–17 - 17 C)

RESET

 

 

 

 

 

 

HRST

0 - 4

0 - 4

HEATING RESET

Not Supported

 

 

TYPE

 

 

 

 

 

 

 

 

HRT1

0° - 125 F

0° - 125 F

NO HEAT RESET

Not Supported

 

 

(–18 - 52 C)

(–18 - 52 C)

TEMP

 

 

 

 

 

 

HRT2

0° - 125 F

0° - 125 F

FULL HEAT RESET

Not Supported

 

 

(–18 - 52 C)

(–18 - 52 C)

TEMP

 

 

 

 

 

 

DGRH

–30 - 30 F

–30 - 30 F

DEGREES HEAT

Not Supported

 

 

(–17 - 17 C)

(–17 - 17 C)

RESET

 

 

 

 

 

 

DMDC

0 - 3

0 - 3

DEMAND LIMIT

Default: 0

 

 

SELECT

 

 

 

 

 

 

 

 

DM20

0 - 100%

0 - 100%

DEMAND LIMIT

Default: 100%

 

 

AT 20 mA

 

 

 

 

 

 

 

 

SHNM

0 - 99

0 - 99

LOADSHED GROUP

Default: 0

 

 

NUMBER

 

 

 

 

 

 

 

 

SHDL

0 - 60%

0 - 60%

LOADSHED DEMAND

Default: 0

 

 

DELTA

 

 

 

 

 

 

 

 

SHTM

0 - 120

0 - 120

MAXIMUM LOADSHED

Default: 60 minutes

 

 

TIME

 

 

 

 

 

 

 

 

DLS1

0 - 100%

0 - 100%

DEMAND LIMIT

Default: 80%

 

 

SWITCH 1

 

 

 

 

 

 

 

 

DLS2

0 - 100%

0 - 100%

DEMAND LIMIT

Default: 50%

 

 

SWITCH 2

 

 

 

 

 

 

 

 

LLEN

ENBL-DSBL

ENBL-DSBL

LEAD/LAG CHILLER

Default: DSBL

 

 

ENABLE

 

 

 

 

 

 

 

 

MSSL

SLVE-MAST

SLVE-MAST

MASTER/SLAVE

Default: Master

 

 

SELECT

 

 

 

 

 

 

 

 

SLVA

0 - 239

0 - 239

SLAVE ADDRESS

Default: 0

 

 

LLBL

ENBL-DSBL

ENBL-DSBL

LEAD/LAG BALANCE

Default: DSBL

 

 

SELECT

 

 

 

 

 

 

 

 

LLBD

40 - 400HRS

40 - 400HRS

LEAD/LAG BALANCE

Default: 168 hours

 

 

DELTA

 

 

 

 

 

 

 

 

LLDY

0 - 30 MIN

0 - 30 MIN

LAG START DELAY

Default: 5 minutes

 

 

 

 

37

 

 