CUT ALONG DOTTED LINECUT ALONG DOTTED LINE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

C.Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY.

RECORD CONFIGURATION INFORMATION BELOW:

OPTIONS2 (Options Configuration)

ITEM

DESCRIPTION

 

STATUS

UNITS

VALUE

CTRL

Control Method

0 = Switch

 

 

 

 

1

= 7 day sched.

 

 

 

 

2

= Occupancy

 

 

 

 

3

= CCN

 

 

CCNA

CCN Address

1 to 239

 

 

CCNB

CCN Bus Number

0 to 239

 

 

BAUD

CCN Baud Rate

1 = 240

 

 

 

 

2

= 480

 

 

 

 

3

= 9600

 

 

 

 

4

= 19,200

 

 

 

 

5

= 38,400

 

 

LOAD

Loading Sequence Select

1 = Equal loading

 

 

 

 

2

= Staged loading

 

 

LLCS

Lead/Lag Circuit Select

1 = Automatic

 

 

 

 

2

= Circuit A leads

 

 

 

 

3

= Circuit B leads

 

 

LCWT

High LCW Alert Limit

2 to 60

^F

 

DELY

Minutes off time

0 to 15

min.

 

ICE.M

Ice Mode Enable

Enable/Disable

 

 

PRESS ESCAPE KEY TO DISPLAY ‘OPT2’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’. PRESS ENTER KEY.

RECORD CONFIGURATION INFORMATION BELOW:

RESETCON (Temperature Reset and Demand Limit)

ITEM

DESCRIPTION

 

STATUS

UNITS

VALUE

 

COOLING RESET

 

 

 

 

CRST

Cooling Reset Type

0

= No Reset

 

 

 

 

1

= 4-20 mA input

 

 

 

 

2

= External temp-OAT

 

 

 

 

3

= Return fluid

 

 

 

 

4

= External temp-SPT

 

 

CRT1

No Cool Reset Temp

0 to 125

°F

 

CRT2

Full Cool Reset Temp

0 to 125

°F

 

DGRC

Degrees Cool Reset

–30 to 30

^F

 

HRST

Heating Reset Type

0

= No Reset

 

 

 

 

1

= 4-20 mA input

 

 

 

 

2

= External temp-OAT

 

 

 

 

3

= Return fluid

 

 

 

 

4

= External temp-SPT

 

 

HRT1

No Heat Reset Temp

Not Supported

°F

 

HRT2

Full Heat Reset Temp

Not Supported

°F

 

DGRH

Degrees Heat Reset

–30 to 30

^F

 

 

DEMAND LIMIT

 

 

 

 

DMDC

Demand Limit Select

0 = None

0

 

 

 

1

= External switch input

 

 

 

 

2

= 4-20 ma input

 

 

 

 

3

= Loadshed

 

 

DM20

Demand Limit at 20mA

0 to 100

%

 

SHNM

Loadshed Group Number

0 to 99

 

 

SHDL

Loadshed Demand Delta

0 to 60

%

 

SHTM

Maximum Loadshed Time

0 to 120

min

 

DLS1

Demand Limit Switch 1

0 to 100

%

 

DLS2

Demand Limit Switch 2

0 to 100

%

 

 

LEAD/LAG

 

 

 

 

LLEN

Lead/Lag Chiller Enable

Enable/Disable

 

 

MSSL

Master/Slave Select

Slave/Master

 

 

SLVA

Slave Address

0 to 239

 

 

LLBL

Lead/Lag Balance Select

Enable/Disable

 

 

LLBD

Lead/Lag Balance Delta

40 to 400

hours

 

LLDY

Lag Start Delay

0 to 30

min

 

CL-5