C. Unit Start-Up (cont)

UNIT (Configuration Settings)

ITEM

DESCRIPTION

 

STATUS

UNITS

VALUE

TYPE

Unit Type

1

= Air Cooled

 

 

 

 

2

= Water Cooled

 

 

 

 

3

= Split System

 

 

 

 

4

= Heat Machine

 

 

 

 

5

= Air Cooled Heat Reclaim

 

 

 

 

 

 

 

TONS

Unit Size

15 to 300

TONS

 

CAP.A

Circuit A1% Capacity

0 to 100

%

 

CMP.A

Number Circ A Compressor

1 to 4

 

 

CYL.A

Compressor A1 Cylinders

4 or 6

 

 

CMP.B

Number Circ B Compressor

1 to 4

 

 

CYL.B

Compressor B1 Cylinders

4 or 6

 

 

EXV

EXV Module Installed

No/Yes

 

 

SH.SP

EXV Superheat Setpoint

10 to 40

^F

 

SH.OF

EXV Superheat Offset

–20 to 20

^F

 

REFG

Refrigerant

1

= R22 2 = R134A

 

 

FAN.S

Fan Staging Select

1

= 2 Stage indpt.

 

 

 

 

2

= 3 Stage indpt.

 

 

 

 

3

= 2 Stage common

 

 

 

 

4

= 3 Stage common

 

 

PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:

OPTIONS1 (Options Configuration)

ITEM

DESCRIPTION

 

STATUS

VALUE

FLUD

Cooler Fluid

1

= Water

 

 

 

2

= Med. Brine

 

 

 

3

= Low Brine

 

HGB.S

Hot Gas Bypass Select

No/Yes

 

HPCM

Head Press. Cont. Method

1

= EXV controlled

 

 

 

2

= Setpoint controlled

 

 

 

3

= Setpoint-A, EXV-B

 

 

 

4

= EXV-A, Setpoint-B

 

HPCT

Head Press. Control Type

0

= None

 

 

 

1

= Air Cooled

 

 

 

2

= Water Cooled

 

MMR.S

Motormaster Select

No/Yes

 

PRTS

Pressure Transducer

No/Yes

 

PMP.I

Cooler Pump Interlock

Off/On

 

CPC

Cooler Pump Control

Off/On

 

CNP.I

Condenser Pump Interlock

Off/On

 

CNPC

Condenser Pump Control

0

= No Control

 

 

 

1

= On with Mode

 

 

 

2

= On with Compressor(s)

 

CWT.S

Condenser Fluid Sensors

No/Yes

 

CA.UN

No. Circuit A Unloaders

0-2

 

CB.UN

No. Circuit B Unloaders

0-2

 

EMM

EMM Module Installed

No/Yes

 