Carrier Air Conditioner Alarm and Alert Codes cont, CCN command for, Manual once con

Models: Air Conditioner

1 96
Download 96 pages 57.36 Kb
Page 51
Image 51

Table 29 — Alarm and Alert Codes (cont)

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

A150

Alarm

Emergency Stop

CCN emergency stop

Chiller shutdown

Automatic once

CCN Network

 

 

 

command received

without going

CCN command for

command.

 

 

 

 

through pumpdown.

EMSTOP returns

 

 

 

 

 

 

to normal

 

A151

Alarm

Illegal Configuration

One or more of the ille-

Chiller is not

Manual once con-

Configuration

 

 

 

gal configurations

allowed to start.

figuration errors

error. See Note on

 

 

 

exists.

 

are corrected

page 52.

A152

Alarm

Unit Down Due to

Both circuits are down

Chiller is unable

Automatic once

Alarm notifies user

 

 

Failure

due to alarms/alerts.

to run.

alarms/alerts are

that chiller is100%

 

 

 

 

 

cleared that pre-

down.

 

 

 

 

 

vent the chiller

 

 

 

 

 

 

from starting.

 

T153

Alert

Real Time Clock

Internal clock on MBB

Occupancy sched-

Automatic when

Time/Date/Month/

 

 

Hardware Failure

fails

ule will not be used.

correct clock con-

Day/Year not prop-

 

 

 

 

Chiller defaults to

trol restarts.

erly set.

 

 

 

 

Local On mode.

 

 

A154

Alarm

Serial EEPROM

Hardware failure with

Chiller is unable

Manual

Main Base Board

 

 

Hardware Failure

MBB

to run.

 

failure.

T155

Alert

Serial EEPROM

Configuration/storage

No Action

Manual

Potential failure of

 

 

Storage Failure

failure with MBB

 

 

MBB. Download

 

 

 

 

 

 

current operating

 

 

 

 

 

 

software. Replace

 

 

 

 

 

 

MBB if error

 

 

 

 

 

 

occurs again.

A156

Alarm

Critical Serial

Configuration/storage

Chiller is not

Manual

Main Base Board

 

 

EEPROM Storage

failure with MBB

allowed to run.

 

failure.

 

 

Failure

 

 

 

 

A157

Alarm

A/D Hardware

Hardware failure with

Chiller is not

Manual

Main Base Board

 

 

Failure

peripheral device

allowed to run.

 

failure.

T170

Alert

Loss of Communica-

MBB loses communica-

Compressors A3,

Automatic

Wiring error, faulty

 

 

tion with CXB

tion with CXB

A4 and B3 and

 

wiring or failed

 

 

 

 

unloaders A2/B2

 

CXB module.

 

 

 

 

unable to operate.

 

 

A172

Alarm

Loss of Communica-

MBB loses communica-

Chiller shutdown

Automatic

Wiring error, faulty

 

 

tion with EXV

tion with EXV

without going

 

wiring or failed

 

 

 

 

through pumpdown.

 

EXV module.

T173

Alert

Loss of Communica-

MBB loses communica-

4 to 20 mA tempera-

Automatic

Wiring error, faulty

 

 

tion with EMM

tion with EMM

ture reset disabled.

 

wiring or failed

 

 

 

 

Demand Limit set to

 

Energy Manage-

 

 

 

 

100%. 4 to 20 mA

 

ment Module

 

 

 

 

set point disabled.

 

(EMM).

T174

Alert

4 to 20 mA Cooling

If configured with EMM

Set point function

Automatic

Faulty signal gen-

 

 

Set Point Input Fail-

and input less than

disabled. Chiller

 

erator, wiring

 

 

ure

2 mA or greater than

controls to CSP.1.

 

error, or faulty

 

 

 

22 mA

 

 

EMM.

T176

Alert

4 to 20 mA Tempera-

If configured with EMM

Reset function dis-

Automatic

Faulty signal gen-

 

 

ture Reset Input

and input less than

abled. Chiller

 

erator, wiring

 

 

Failure

2 mA or greater than

returns to normal

 

error, or faulty

 

 

 

22 mA

set point control.

 

EMM.

T177

Alert

4 to 20 mA Demand

If configured with EMM

Demand limit func-

Automatic

Faulty signal gen-

 

 

Limit Input Failure

and input less than

tion disabled. Chiller

 

erator, wiring

 

 

 

2 mA or greater than

returns to 100%

 

error, or faulty

 

 

 

22 mA

demand limit

 

EMM.

 

 

 

 

control.

 

 

 

 

 

 

 

 

 

A200

Alarm

Cooler Pump Inter-

Interlock not closed

Cooler pump shut

Manual

Failure of cooler

 

 

lock Failure to Close

within 5 minutes after

off. Chiller shutdown

 

pump, flow switch,

 

 

at Start-Up

unit is started

without going

 

or interlock.

 

 

 

 

through pumpdown.

 

 

A201

Alarm

Cooler Pump Inter-

Interlock opens during

Cooler pump shut

Manual

Failure of cooler

 

 

lock Opened During

operation

off. Chiller shutdown

 

pump, flow switch,

 

 

Normal Operation

 

without going

 

or interlock.

 

 

 

 

through pumpdown.

 

 

A202

Alarm

Cooler Pump Inter-

If configured for cooler

Chiller is not

Manual

Failure of cooler

 

 

lock Closed When

pump control and inter-

allowed to start.

 

pump relay or

 

 

Pump is Off

lock closes while cooler

 

 

interlock, welded

 

 

 

pump relay is off

 

 

contacts.

 

 

 

 

 

 

 

51

Page 51
Image 51
Carrier Air Conditioner specifications Alarm and Alert Codes cont, CCN command for, Manual once con