Table 29 — Alarm and Alert Codes (cont)
ALARM/ | ALARM |
| WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE | |
ALERT | OR | DESCRIPTION | ALARM | ||||
BY CONTROL | METHOD | CAUSE | |||||
CODE | ALERT |
| GENERATED? | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
A150 | Alarm | Emergency Stop | CCN emergency stop | Chiller shutdown | Automatic once | CCN Network | |
|
|
| command received | without going | CCN command for | command. | |
|
|
|
| through pumpdown. | EMSTOP returns |
| |
|
|
|
|
| to normal |
| |
A151 | Alarm | Illegal Configuration | One or more of the ille- | Chiller is not | Manual once con- | Configuration | |
|
|
| gal configurations | allowed to start. | figuration errors | error. See Note on | |
|
|
| exists. |
| are corrected | page 52. | |
A152 | Alarm | Unit Down Due to | Both circuits are down | Chiller is unable | Automatic once | Alarm notifies user | |
|
| Failure | due to alarms/alerts. | to run. | alarms/alerts are | that chiller is100% | |
|
|
|
|
| cleared that pre- | down. | |
|
|
|
|
| vent the chiller |
| |
|
|
|
|
| from starting. |
| |
T153 | Alert | Real Time Clock | Internal clock on MBB | Occupancy sched- | Automatic when | Time/Date/Month/ | |
|
| Hardware Failure | fails | ule will not be used. | correct clock con- | Day/Year not prop- | |
|
|
|
| Chiller defaults to | trol restarts. | erly set. | |
|
|
|
| Local On mode. |
|
| |
A154 | Alarm | Serial EEPROM | Hardware failure with | Chiller is unable | Manual | Main Base Board | |
|
| Hardware Failure | MBB | to run. |
| failure. | |
T155 | Alert | Serial EEPROM | Configuration/storage | No Action | Manual | Potential failure of | |
|
| Storage Failure | failure with MBB |
|
| MBB. Download | |
|
|
|
|
|
| current operating | |
|
|
|
|
|
| software. Replace | |
|
|
|
|
|
| MBB if error | |
|
|
|
|
|
| occurs again. | |
A156 | Alarm | Critical Serial | Configuration/storage | Chiller is not | Manual | Main Base Board | |
|
| EEPROM Storage | failure with MBB | allowed to run. |
| failure. | |
|
| Failure |
|
|
|
| |
A157 | Alarm | A/D Hardware | Hardware failure with | Chiller is not | Manual | Main Base Board | |
|
| Failure | peripheral device | allowed to run. |
| failure. | |
T170 | Alert | Loss of Communica- | MBB loses communica- | Compressors A3, | Automatic | Wiring error, faulty | |
|
| tion with CXB | tion with CXB | A4 and B3 and |
| wiring or failed | |
|
|
|
| unloaders A2/B2 |
| CXB module. | |
|
|
|
| unable to operate. |
|
| |
A172 | Alarm | Loss of Communica- | MBB loses communica- | Chiller shutdown | Automatic | Wiring error, faulty | |
|
| tion with EXV | tion with EXV | without going |
| wiring or failed | |
|
|
|
| through pumpdown. |
| EXV module. | |
T173 | Alert | Loss of Communica- | MBB loses communica- | 4 to 20 mA tempera- | Automatic | Wiring error, faulty | |
|
| tion with EMM | tion with EMM | ture reset disabled. |
| wiring or failed | |
|
|
|
| Demand Limit set to |
| Energy Manage- | |
|
|
|
| 100%. 4 to 20 mA |
| ment Module | |
|
|
|
| set point disabled. |
| (EMM). | |
T174 | Alert | 4 to 20 mA Cooling | If configured with EMM | Set point function | Automatic | Faulty signal gen- | |
|
| Set Point Input Fail- | and input less than | disabled. Chiller |
| erator, wiring | |
|
| ure | 2 mA or greater than | controls to CSP.1. |
| error, or faulty | |
|
|
| 22 mA |
|
| EMM. | |
T176 | Alert | 4 to 20 mA Tempera- | If configured with EMM | Reset function dis- | Automatic | Faulty signal gen- | |
|
| ture Reset Input | and input less than | abled. Chiller |
| erator, wiring | |
|
| Failure | 2 mA or greater than | returns to normal |
| error, or faulty | |
|
|
| 22 mA | set point control. |
| EMM. | |
T177 | Alert | 4 to 20 mA Demand | If configured with EMM | Demand limit func- | Automatic | Faulty signal gen- | |
|
| Limit Input Failure | and input less than | tion disabled. Chiller |
| erator, wiring | |
|
|
| 2 mA or greater than | returns to 100% |
| error, or faulty | |
|
|
| 22 mA | demand limit |
| EMM. | |
|
|
|
| control. |
|
| |
|
|
|
|
|
|
| |
A200 | Alarm | Cooler Pump Inter- | Interlock not closed | Cooler pump shut | Manual | Failure of cooler | |
|
| lock Failure to Close | within 5 minutes after | off. Chiller shutdown |
| pump, flow switch, | |
|
| at | unit is started | without going |
| or interlock. | |
|
|
|
| through pumpdown. |
|
| |
A201 | Alarm | Cooler Pump Inter- | Interlock opens during | Cooler pump shut | Manual | Failure of cooler | |
|
| lock Opened During | operation | off. Chiller shutdown |
| pump, flow switch, | |
|
| Normal Operation |
| without going |
| or interlock. | |
|
|
|
| through pumpdown. |
|
| |
A202 | Alarm | Cooler Pump Inter- | If configured for cooler | Chiller is not | Manual | Failure of cooler | |
|
| lock Closed When | pump control and inter- | allowed to start. |
| pump relay or | |
|
| Pump is Off | lock closes while cooler |
|
| interlock, welded | |
|
|
| pump relay is off |
|
| contacts. | |
|
|
|
|
|
|
|