Table 15 — Outputs Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

RANGE

ITEM EXPANSION

COMMENT

ENTRY

 

 

 

 

 

GEN.O

ENTER

FAN1

OFF-ON

FAN 1 RELAY

 

 

 

FAN2

OFF-ON

FAN 2 RELAY

 

 

 

FAN3

OFF-ON

FAN 3 RELAY

 

 

 

FAN4

OFF-ON

FAN 4 RELAY

 

 

 

C.PMP

OFF-ON

COOLER PUMP RELAY

 

 

 

H.GAS

OFF-ON

HOT GAS BYPASS RELAY

 

 

 

CNDP

OFF-ON

CONDENSER PUMP RELAY

 

CIR.A

ENTER

CC.A1

OFF-ON

COMPRESSOR A1 RELAY

 

 

 

 

 

CC.A2

OFF-ON

COMPRESSOR A2 RELAY

 

 

 

CC.A3

OFF-ON

COMPRESSOR A3 RELAY

 

 

 

CC.A4

OFF-ON

COMPRESSOR A4 RELAY

 

 

 

ULA1

OFF-ON

UNLOADER A1 RELAY

 

 

 

ULA2

OFF-ON

UNLOADER A2 RELAY

TXV units only

 

 

LLS.A

OPEN-CLSE

LIQUID LINE SOLENOID VLV

EXV units only

 

 

EXV.A

0 - 100%

EXV % OPEN

 

CIR.B

ENTER

CC.B1

OFF-ON

COMPRESSOR B1 RELAY

 

 

 

 

 

CC.B2

OFF-ON

COMPRESSOR B2 RELAY

 

 

 

CC.B3

OFF-ON

COMPRESSOR B3 RELAY

 

 

 

CC.B4

OFF-ON

COMPRESSOR B4 RELAY

 

 

 

ULB1

OFF-ON

UNLOADER B1 RELAY

 

 

 

ULB2

OFF-ON

UNLOADER B2 RELAY

 

 

 

LLS.B

OPEN-CLSE

LIQUID LINE SOLENOID VLV

TXV units only

 

 

EXV.B

0 - 100%

EXV % OPEN

EXV units only

LEGEND

 

 

 

 

 

EXV — Electronic Expansion Valve

TXV — Thermostatic Expansion Valve

Table 16 — Configuration Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

MARQUEE

NAVIGATOR

ITEM EXPANSION

 

COMMENT

ENTRY

DISPLAY RANGE

DISPLAY RANGE

 

 

 

 

 

 

DISP

ENTER

TEST

OFF-ON

OFF-ON

TEST DISPLAY

 

 

 

LEDS

 

 

 

 

 

 

 

 

 

 

 

METR

OFF-ON

OFF-ON

METRIC DISPLAY

Off = English

 

 

On = Metric

 

 

 

 

 

 

 

 

LANG

0 - 3

ENGLISH

LANGUAGE

Default: 0

 

 

 

 

ESPANOL

SELECTION

0

= English

 

 

 

 

FRANCAIS

 

1

= Espanol

 

 

 

 

PORTUGUES

 

2

= Francais

 

 

 

 

 

 

3

= Portugues

LEGEND

 

 

 

 

 

 

 

CCN — Carrier Comfort Network

EMM — Energy Management Module

EXV — Electronic Expansion Valve

LCW — Leaving Chilled Water