Carrier 50FK, JK034-074, 48FK specifications Start Unit

Models: 48FK 50FK JK034-074

1 60
Download 60 pages 6.49 Kb
Page 31
Image 31
START UNIT

START UNIT

To start unit:

1.Close the unit-mounted ON/OFF switch (located in the main control box).

2.Close the ®eld-supplied and -installed timeclock (or con- trol) switch (contacts located at Terminals 1 and 2 (TB3 for 034-048, TB4 for 054-104).

IMPORTANT: The ®eld-supplied and installed switch (or timeclock) MUST BE CLOSED to put unit in Occupied mode. Unit WILL NOT START until this is accomplished.

3.Initialization mode begins (see Operating Information sec- tion on page 34 for complete description of sequences and display codes).

4.Run Quick Test. If the display button is pressed during the initialization mode period, the unit will run its self-

diagnostic routine. When this is in effect, an 88 will ap-

pear in the display screen. Refer to Quick Test Program section below, for instructions on completing the Quick Test program.

Quick Test Program Ð Turn on power to unit.

IMPORTANT: The ®eld-supplied switch (or time- clock) must be closed to put unit into the occupied mode.

The quick test program utilizes the 2-digit LED display (see Fig. 6) on the set point board to show status of all input and output signals to microprocessor. Display action and quick test procedures are described below.

The quick test program is a 33-step program that provides a means of checking all input and output signals of controls prior to unit start-up. This check ensures that all control op- tions, thermistors, and control switches are in proper work- ing order.

When unit control circuit is switched to Occupied mode,

a20 will appear on the display. Immediately press display button once. An 88 will appear on the display and alarm

light on display board will be energized. This indicates that control system is ready to run quick test program.

IMPORTANT: Do not allow unit control circuit to

remain energized with 20 showing on display for more

than 2 minutes. If display button is not pressed within this time period, control will attempt to start unit.

For each step of the 33-step program, display button must be pressed twice. On ®rst press, step number is displayed; second press initiates required action and appropriate code is displayed.

NOTE: The step number is a numeral followed by a decimal point (a 2-digit number has a decimal point after each nu- meral). The action code number is one or 2 digits with no decimal point(s).

IMPORTANT: Once quick test is initiated, display but- ton must be pressed at least once every 10 minutes for control to remain in quick test mode. If button is not pressed within this time, control will attempt to start the unit.

To recheck any step in quick test program, control must be recycled by turning unit control switch off for a few sec- onds, and then turning it back on again. Restart quick test program as described above and proceed through quick test steps. Press display button twice for each step until step to be rechecked is reached.

The quick test program is divided into 3 sections as de- scribed below and shown in Tables 15-17.

1.Quick Test Steps 1.-1.3. Ð Unit Con®guration and Switch Check

The microprocessor in unit control system is programmed by 2 switch assemblies located on processor board (Fig. 1). The con®guration header is factory set and can- not be changed in the ®eld. The DIP switch assembly con- tains 8 microswitches that must be set in accordance with the various options selected by the customer. All DIP switches should be checked and set to proper position for options selected prior to the quick test. See Con®guration of Header and DIP Switch Assembly section on page 5 for factory switch settings. The DIP switch functions and display codes are shown in Table 15.

2.Quick Test Steps 1.4.-2.3. Ð Thermistor and Set Point Potentiometer Check

In these steps, the microprocessor checks resistance val- ues of all sensors and set point potentiometers to ensure that they are functional, connected properly, and set within proper range for unit con®guration.

Nominal resistance values for all sensors range from 363,000 to 219 ohms in accordance with Table 18. Normal dis- play code for good sensors and potentiometers is 1. A dis- play code of 0 indicates a faulty potentiometer, thermistor or wiring. A 0 display also indicates that option is not being used.

Table 16 shows thermistor and set point potentiometer functions and quick test display codes.

31

Page 31
Image 31
Carrier 50FK, JK034-074, 48FK specifications Start Unit