Diagnostic Codes Ð Diagnostic codes are warnings of abnormal or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assigned code numbers as described below.

Table 22 contains a description of each diagnostic code error and possible cause. Manual reset is accomplished by moving the ON/OFF Switch to the OFF position, then back to ON.

The 2-digit LED display is used to display the diagnostic codes and the alarm light (located next to display) is ener- gized whenever a diagnostic code is tripped. When a prob- lem is suspected, always check the display ®rst for diagnos- tic information.

NOTE: Codes 53, 54, 57, 58, 61, 62, 65-69, 73, 74, and 77-80 are not used on these units.

IMPORTANT: The microprocessor memory and the display will be cleared if the power to the microproces- sor is shut off. DO NOT attempt to bypass, short, or modify the control circuit or electronic boards in any way to correct a problem. This could result in a haz- ardous operating condition.

CODES 51, 52, 55, 56: COMPRESSOR FAILURE Ð If con- trol relay (CR) opens while compressor should be operating, compressor will stop and microprocessor will energize alarm

light and display a code of 51 , 52 , 55 or 56 (de-

pending on compressor) when display button is pushed. The compressor will be locked off; to reset, the ON-OFF switch must be turned to OFF and then to ON position.

If lead compressor in a refrigerant circuit is shut down, the other compressor in that circuit will also be shut down and locked off. Only the error code for the lead compressor will be displayed.

Code 51 is for compressor 1, and Code 55 is for com- pressor 2. Codes 52 and 56 are used for compressors 3 and 4, respectively, on size 104 units.

The microprocessor has also been programmed to indi- cate a compressor failure if CR switch is closed when com- pressor is not supposed to be on.

If a failure occurs, the following are possible causes:

High-Pressure Switch Open Ð The high-pressure switch for each compressor is wired in series with 24-v power that en- ergizes CR. If high-pressure switch opens during operation, CR will stop compressor and this will be detected by micro- processor through the feedback contacts.

Internal Thermostat Ð The internal thermostat in each 06D compressor is also wired in series with 24-v power that en- ergizes CR. If thermostat fails or switch opens during op- eration of compressor, compressor will shut down and fail- ure is detected through feedback contacts (size 034 and 038 only).

CR Failure Ð If CR fails with large relay either open or closed, microprocessor will detect this, lock compressor off, and in- dicate an error.

Relay Board Failure Ð If small 24-v relay on the relay board fails, microprocessor will detect this through feedback con- tacts and indicate an error.

Processor Board Failure Ð If hardware that monitors feed- back switch fails and processor board fails to energize the relay board relay to ON position, an error may be indicated.

The control does not detect compressor circuit breaker failures.

Wiring Problem Ð A wiring error or a loose wire may cause the feedback circuit to be broken.

Table 22 Ð Diagnostic Codes

DISPLAY

DESCRIPTION OF FAILURE

ACTION TAKEN

RESET

PROBABLE CAUSE

 

 

BY CONTROL

METHOD

 

51

Compressor 1 failure

Circuit 1 shut off

Manual

High-pressure switch or high dis-

55

Compressor 2 failure

Circuit 2 shut off

Manual

charge gas thermostat switch

52

Compressor 3 failure

Compressor 3 shut off

Manual

trip, compressor ground current

56

Compressor 4 failure

Compressor 4 shut off

Manual

. 2.5 amp or compressor board

 

 

 

 

relay on when it is not supposed

 

 

 

 

to be on. Wiring error between

 

 

 

 

electronic control and compres-

 

 

 

 

sor protection module.

59

Loss-of-charge circuit 1

Circuit 1 shut off

Manual

This indicates either a low refrig-

60

Loss-of-charge circuit 2

Circuit 2 shut off

Manual

erant charge, or a loss-of-charge

 

 

 

 

switch failure.

63

Low oil pressure circuit 1

Circuit 1 shut off

Manual

Not used; Check jumper on pro-

64

Low oil pressure circuit 2

Circuit 2 shut off

Manual

cessor board.

70

Illegal unit con®guration

Unit will not start

Manual

Con®guration error (see Note 1).

71

Supply-air thermistor failure

Unit shut off

Auto.

Thermistor or resistor failure, wir-

72

Return-air thermistor failure

Use default value

Auto.

ing error, or thermistor or resistor

75

Circuit 1 saturated condensing thermistor

Unit shut off

Auto.

not connected to the processor

76

Circuit 2 saturated condensing thermistor

Unit shut off

Auto.

board.

 

81

Reset temperature thermistor failure

Stop reset

Auto.

 

82

Leaving-air set point potentiometer failure

Use default value

Auto.

Potentiometer improperly con-

83

Economizer potentiometer failure

Close economizer

Auto.

nected, potentiometer setting out

84

Reset limit set point potentiometer failure

Stop reset

Auto.

of range, potentiometer failure or

85

Demand limit potentiometer failure

Stop demand limit

Auto.

wiring error.

86

Minimum economizer potentiometer failure

Close economizer

Auto.

 

87

Warm-up set point potentiometer failure

Use default value

Auto.

 

NOTES:

1.Illegal unit con®guration caused by missing programmable header or both unloader DIP switches on.

2.All auto. reset failures that cause the unit to stop will restart when the error has been corrected.

3.All manual reset errors must be reset by turning the control switch off and then back on.

4.Valid resistance range for the thermistors is 363,000 to 585 ohms.

5.Codes 53, 54, 57, 58, 61, 62, 65-69, 73, 74, and 77-80 are not used on these units.

45

Page 45
Image 45
Carrier JK034-074, 50FK, 48FK specifications Diagnostic Codes