Carrier 48FK, 50FK Ð Switch Functions, Ð Tubing Size, SIZE in, Inlet Guide Vanes IGV, Drive VFD

Models: 48FK 50FK JK034-074

1 60
Download 60 pages 6.49 Kb
Page 23
Image 23

Table 7 Ð Switch Functions

 

SWITCH

 

CONFIGURATION

VOLTAGE

FUNCTION

 

NUMBER

 

 

 

 

 

 

 

 

SW-1

 

 

N.C.

115

Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)

 

SW-2

 

 

N.C.

115

Deenergize TRAN7 (Process Board)

 

SW-3

 

 

N.O.

24

Energize EOR (Open Economizer Outside Air Dampers)

 

SW-4

 

 

N.O.

115

Energize IFC and CR-3 (IGV/VFD)

 

SW-5

 

 

N.C.

115

Isolate IFC and PEC for Separate Operation

 

SW-6

 

 

N.O.

115

Energize PEC (Power Exhaust)

 

SW-7

 

 

N.O.

24

Open PED at DPS

 

SW-8

 

 

N.C.

24

Block Auto-Close at DPS (Due to Low BP)

 

SW-9A/B

 

 

A: N.O.

115 max

Signal Room Terminals to Open (HIR1)

 

 

 

B: N.C.

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

BP

Ð Building Pressure

 

 

 

 

DPS

Ð Differential Pressure Switch

 

 

EOR Ð Economizer Open Relay

 

 

HIR

Ð

Heat Interlock Relay

 

 

 

IFC

Ð

Indoor Fan Contactor

 

 

 

IGV

Ð

Inlet Guide Vane

 

 

 

 

N.C.

Ð

Normally Closed

 

 

 

 

N.O.

Ð

Normally Open

 

 

 

 

PEC

Ð Power Exhaust Contactor

 

 

PED

Ð Power Exhaust Damper

 

 

OFC

Ð Outdoor Fan Contactor

 

 

 

VFD

Ð Variable Frequency Drive

 

 

Air Pressure Tubing Ð Before options such as inlet guide vanes (IGV), variable frequency drive (VFD), and/or modulating power exhaust can operate properly, the pneu- matic tubing for pressure sensing must be installed. Use ®re- retardent plenum tubing (®eld-supplied). Tubing size depends on type of control device (see Table 8 below). Tubing must be run from the appropriate sensing location (in the duct or in the building space) to the control device location in the unit.

Table 8 Ð Tubing Size

OPTION

UNITS

NOMINAL TUBE

SIZE (in.)

 

 

Inlet Guide Vanes (IGV)

ALL

3¤8

Variable Frequency

ALL

1¤4

Drive (VFD)

 

 

Modulating Power Exhaust

FK,FKX,JK,JKX

3¤8

INLET GUIDE VANES Ð The tubing for the duct pressure (DP) control option should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.

The inlet guide vanes are controlled by a differential pres- sure switch (DPS). On sizes 034-048, the DPS is located in the auxiliary control box at the economizer end of the unit (see Fig. 33). On sizes 054-104, the DPS is located in the supply fan section. See Fig. 34. Use a nominal 3¤8-in. plastic tubing.

VARIABLE FREQUENCY DRIVE Ð The tubing for the duct pressure (DP) control option should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.

The duct pressure is sensed by a pressure transducer. The pressure transducer output is directed to the VFD. On 034- 048 units the DP transducer is located in the auxiliary con- trol box. On 054-104 units, the DP transducer is located in the supply fan section. See Fig. 34. Use a nominal 1¤4-in. plastic tubing.

23

Page 23
Image 23
Carrier 48FK, JK034-074 Ð Switch Functions, Ð Tubing Size, SIZE in, Inlet Guide Vanes IGV, Variable Frequency, Drive VFD