Carrier JK034-074 Ð Accessory Relay Board Standard Factory Supplied, Ð Enthalpy Sensor Location

Models: 48FK 50FK JK034-074

1 60
Download 60 pages 6.49 Kb
Page 12
Image 12
Fig. 15 Ð Accessory Relay Board

LEGEND

ECON Ð Economizer

MIN Ð Minimum

PÐ Potentiometer

VAV Ð Variable-Air Volume

Fig. 15 Ð Accessory Relay Board

(Standard; Factory Supplied)

 

 

LEGEND

IC

Ð

Integrated Circuit

IN

Ð

Input

PÐ Potentiometer RTN Ð Return

Fig. 16 Ð Two-Step Demand Limit Module

Fig. 17 Ð Enthalpy Sensor Location

Variable Frequency Drive (VFD) Ð The optional VFD is used to modulate supply fan air¯ow to maintain duct static pressure on VAV applications. The VFD is located in the supply fan section (see Fig. 18 and 19), and can be ac- cessed by opening the fan section access door.

The unit is supplied with a pressure transducer capable of measuring from 0.0 to 5.0 in. wg. The pressure transducer will send a 4 to 20 mA signal to the VFD to modulate the speed of the indoor fan motor to precisely control the fan to the desired static pressure set point. The VFD is factory set at 2.5 in. wg duct static pressure. Refer to the Operating Se- quence section for more information on the VFD.

The VFD has been programmed and wired at the factory for this application. No further adjustments (except for Duct Static Pressure Set Point) should be necessary at start-up. Factory jumper wire con®gurations are shown in the Supply Fan Control with VFD Option section on page 28.

A separate service manual for the factory-installed VFD is supplied with each unit. Refer to the VFD manual for more information on the VFD controls.

Temperature Reset Ð Accessory temperature reset al- lows the unit to automatically adjust (``reset'') the supply- air temperature set point to a higher value once most of the space cooling load has been met. When the space conditions are satis®ed, the VAV terminals will close to the minimum position. All VAV units will sense the decrease in actual supply- air temperature and the unit controls respond by reducing