Carrier 48FK Ð Carrier Default Program Parameter Values, Gr.Fb, Gr.SF, Frequency Settings, Gr.Pn

Models: 48FK 50FK JK034-074

1 60
Download 60 pages 6.49 Kb
Page 53
Image 53

Table 29 Ð Carrier Default Program Parameter Values

PARAMETER GROUP

PARAMETER

DEFAULT VALUE

 

ACC1

60.0 Sec

 

DEC1

60.0 Sec

 

UL

60.0 Hz

 

LL

10.0 Hz*

 

Luln

1

 

P3

20%

SEtP

F-P3

0.0 Hz

(Setup)

P4

100%

 

F-P4

60 Hz

 

tHr1

See Table 31

 

StC1

0

 

StL1

110%

 

OLN

1

 

tYP

5*

Gr.F

FH

60 Hz

(Fundamental)

Pt

2

 

FbP1

1*

 

Fbln

2

 

GP

.30

 

Gl

2 sec

Gr.Fb

GA

0

(Feedback)

GFS

80

 

P1LL

10

 

PuL

1

 

PuUl

10

 

PuLL

10

Gr.SF

Fsor

60 Hz

Sr.n

1* (054-104 only)

(Frequency Settings)

SrN1

0* (054-104 only)

 

Gr.Pn

Fr

0*

(Panel Control)

 

 

 

1t

1

 

1t0

0

Gr.St

1t1

56

(Terminal Selection)

1t2

13

 

1t3

3

 

1t4

10

Gr.Pr

UuC

1*

UuCt

2

(Protection)

ArSt

3

 

 

Cnod

1*

Gr.Ut

bLSF

1* (054-104 only)

(Utility)

Fnod

2*

 

bLPn

1*

*These settings differ from the Toshiba defaults and are required for Carrier applications.

NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SetP). This restores the VFD original factory settings.