INSTALLATION Ð To enable one or more of the possible smoke control modes available with these units, determine the switches required for the desired mode(s) from Table 6, ®eld-supply and install the appropriate switches and ®eld wire per Fig. 32. Switch functions are shown in Table 7.

Table 5 Ð Smoke Control Modes

 

 

MODE

 

 

FUNCTION

Fire

Pressur-

Evacuation*

 

Smoke

 

Shutdown

ization

 

Purge*

 

 

 

Supply Fan

Off

On

Off

 

On

IGV/VFD²

Ð

Open/On

Ð

 

Open/On

Economizer

Closed

Open

Open

 

Open

Return Air

Open

Closed

Closed

 

Closed

Damper

 

 

 

 

 

 

Exhaust

Off

Off

On

 

On

Fans

 

 

 

 

 

 

Exhaust

Closed

Closed

Open

 

Open

Damper

 

 

 

 

 

 

LEGEND

 

 

 

 

IGV Ð Inlet Guide Vane

VAV Ð Variable Air Volume

VFD Ð Variable Frequency Drive

*Power exhaust option/accessory required for this mode. ²Applicable to VAV units with appropriate options.

CONFIGURATION Ð No set points required for Smoke Con- trol modes. Modes are activated by energizing all switches appropriate for each Smoke Control mode.

OPERATING SEQUENCE

Fire Shutdown Ð At command from the ®eld switches (see Table 5), all unit operation (cooling, heating, supply fan and power exhaust) will terminate.

Pressurization Ð At command from the ®eld switches for Pressurization mode (see Table 5):

1.Economizer dampers will open

2.The HIR function will energize, opening room terminals to full-open (heating) positions.

3.Supply fan will run. (If equipped with IGV: control vanes

will open. If equipped with VFD: the VFD will control to duct static set point or best available with all terminals open.)

4.Power exhaust dampers (if equipped) will close.

5.Power exhaust fans (if equipped) will turn off.

Evacuation Ð At command from the ®eld switches for Evacu- ation mode (see Table 5):

1.Supply fan will turn off.

2.Economizer dampers will open.

3.Exhaust fans will run at maximum capacity.

4.Exhaust dampers will open.

Smoke Purge Ð At command from the ®eld switches for Smoke Purge mode (see Table 5):

1.Economizer dampers will open.

2.The HIR function will energize, opening room terminals to full-open (heating) positions.

3.Supply fan will run. (If equipped with IGV: Control vanes

will open. If equipped with VFD: the VFD will control to duct static set point or best available with all terminals open.)

4.Exhaust fans will run at maximum capacity.

5.Exhaust dampers will open.

Table 6 Ð Smoke Control Switches Required for Each Mode

FIRE

 

EVACUATION

SMOKE

PRESSURIZATION

(Modulating Power

SHUTDOWN

PURGE

 

Exhaust)

 

 

 

SW-1

SW-1

SW-1

SW-1

SW-2

SW-2

SW-2

SW-2

 

SW-4

SW-3

SW-3

 

SW-5

SW-5

SW-4

 

SW-6

SW-6

SW-9A/B

 

SW-9A/B

SW-7

 

 

 

SW-8

 

 

 

 

 

NOTE: All switches are shown in ``as installed'' (power OFF or deenergized) position. In these positions, none of these modes will be activated; normal unit operation is permitted by the base unit controls. To initiate any mode, all switches listed under this mode in the table must be energized, causing the depicted contact position to change from depicted positions to energized positions. Switches may be manually or electrically operated.