conversion process is the same for right and left return configu- rations. See Fig. 11 and 12.

NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.

Preparation — The unit should be on the ground in a well lit area for conversion. Hung units should be taken down to ground level before converting.

Side to Back Discharge Conversion

1.

Remove screws to free the top and discharge panels. See

 

Fig. 11.

2.

Remove the access panel and set aside.

3.

Lift the discharge panel from side of unit and rotate it to

 

back using care not to damage blower wiring.

4.

Check blower wire routing and connections for undo

 

tension or contact with sheet metal edges. Re-route if

 

necessary.

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 9 — Typical Vertical Installation —

50RVC,RVR,RVS Units

5.

Check refrigerant tubing for contact with other compo-

 

nents. Adjust if necessary.

6.

Reinstall top panel using screws set aside in Step 1.

Power

Thermostat Wiring

Compressor Access Panel

Flexible

Building

 

Connection

Loop

 

 

Water

Water

 

Out

 

In

 

 

 

 

Balancing Valve

 

 

(field-installed

 

 

and calibrated

 

Field-supplied

accessory)

 

 

 

stainless steel

Low Pressure

 

braid hose

 

with integral

Drop Water

 

“ J” swivel

Control Valve (optional)

 

 

(field-installed

 

 

accessory)

Ball Valve with optional integral P/T plug (typical for supply and return piping)

Flexible

Connection

Supply Air

NOTE: Location for some screws at bottom of discharge panel may have to be changed.

7.Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.

8.Replace access panel.

Back to Side Discharge Conversion — Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.

Water

Remove Screws

Connection End

 

Return Air

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 10 — Typical Downflow Installation —

50RDS Units

Step 3 — Unit Location — The following guidelines should be considered when choosing a location for a WSHP:

Units are for indoor use only.

Locate in areas where ambient temperatures are between 40 F and 100 F and relative humidity is no greater than 75%.

Provide sufficient space for water, electrical and duct connections.

Locate unit in an area that allows easy access and removal of filter and access panels.

Allow enough space for service personnel to perform maintenance.

Return air must be able to freely enter the space if unit needs to be installed in a confined area such as a closet.

NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since duct- work is normally applied to these units, the unit can be placed so that the principal sound emission is outside the oc- cupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.

FIELD CONVERSION OF DISCHARGE AIR — The dis- charge air of the 50RHC,RHR,RHS horizontal units can be converted between side and back discharge in the field. The

Side Discharge

Water

Connection End

Rotate

Return Air

 

Move to Side

Water

Replace Screws

Connection End

 

Return Air

Drain

Back Discharge

Discharge Air

Fig. 11 — Conversion Left Return, Side Discharge to Back Discharge

14

Page 14
Image 14
Carrier RVS, RDS006-060, RVR, RHR Remove Screws, Side Discharge, Rotate, Move to Side, Water Replace Screws Connection End