Carrier RDS006-060, RVR, RHR, RVC, 50RHC Pre-Start-Up, 50RDS, RHS, RVS Electrical Data

Models: 50RHC RHS RVC RHR RVR RDS006-060 RVS

1 44
Download 44 pages 51.02 Kb
Page 26
Image 26

Table 7 — 50RDS, RHS, RVS Electrical Data

50RDS,

VOLTS-

VOLTAGE

COMPRESSOR

FAN

TOTAL

MIN

 

MAX

 

UNITS WITH HWR

 

RHS,

PHASE

 

 

 

MOTOR

UNIT

CIRCUIT

 

REHEAT

TOTAL

MIN

MAX

RVS

MIN/MAX

RLA

 

LRA

 

FUSE/HACR

PUMP

UNIT

CIRCUIT

FUSE /

60 Hz

 

FLA

FLA

AMP

 

UNIT

 

 

 

 

 

 

FLA

FLA

AMP

HACR

 

 

 

 

 

 

 

 

 

 

 

015

208/230-1

197/254

4.9

 

26.0

1.00

 

5.9

7.2

 

15

0.8

6.7

7.9

15

265-1

239/292

4.4

 

28.0

0.86

 

5.2

6.3

 

15

0.7

8.0

7.1

15

 

 

 

 

018

208/230-1

197/254

7.1

 

38.0

1.00

 

8.1

9.8

 

15

0.8

8.9

10.7

15

265-1

239/292

5.5

 

32.0

0.86

 

6.4

7.8

 

15

0.7

7.1

8.5

15

 

 

 

 

 

208/230-1

197/254

10.3

 

56.0

1.10

11.4

13.9

 

20

0.8

12.8

15.5

25

024

265-1

239/292

8.7

 

47.0

0.90

 

9.6

11.7

 

20

0.7

10.6

12.9

20

208/230-3

197/254

7.1

 

45.0

1.10

 

8.2

9.9

 

15

0.8

9.0

10.8

20

 

 

 

 

 

460-3

414/506

3.5

 

22.4

0.57

 

4.1

5.0

 

15

0.7

4.8

5.7

15

 

208/230-1

197/254

12.2

 

67.0

1.30

13.5

16.5

 

25

0.8

14.3

17.4

25

030

265-1

239/292

10.9

 

56.0

1.58

12.5

15.2

 

25

0.7

13.2

15.9

25

208/230-3

197/254

7.7

 

55.0

1.30

 

9.0

10.9

 

15

0.8

9.8

11.7

15

 

 

 

 

 

460-3

414/506

3.8

 

27.0

0.85

 

4.7

5.7

 

15

0.7

5.4

6.4

15

030

208/230-1

197/254

12.2

 

67.0

1.30

13.5

16.5

 

25

0.8

14.8

17.9

30

265-1

239/292

10.9

 

56.0

1.58

12.5

15.2

 

25

0.7

13.6

16.3

25

HIGH

 

 

208/230-3

197/254

7.7

 

55.0

1.30

 

9.0

10.9

 

15

0.8

10.3

12.2

15

STATIC

 

 

 

 

460-3

414/506

3.8

 

27.0

0.85

 

4.7

5.7

 

15

0.7

5.8

6.8

15

 

208/230-1

197/254

13.5

 

73.0

1.80

15.3

18.6

 

30

0.8

16.1

19.5

30

036

265-1

239/292

12.8

 

71.0

2.00

14.8

18.0

 

30

0.7

15.5

18.7

30

208/230-3

197/254

9.6

 

63.0

1.80

11.4

13.8

 

20

0.8

12.2

14.6

20

 

 

 

 

460-3

414/506

4.5

 

31.0

1.24

 

5.7

6.8

 

15

0.7

6.5

7.6

15

036

208/230-1

197/254

13.5

 

73.0

1.80

15.3

18.6

 

30

0.8

17.3

20.7

30

265-1

239/292

12.8

 

71.0

2.00

14.8

18.0

 

30

0.7

16.2

19.4

30

HIGH

 

 

208/230-3

197/254

9.6

 

63.0

1.80

11.4

13.8

 

20

0.8

13.4

15.8

25

STATIC

 

 

 

460-3

414/506

4.5

 

31.0

1.24

 

5.7

6.8

 

15

0.7

6.9

8.0

15

 

208/230-1

197/254

16.5

 

95.0

1.90

18.4

22.6

 

35

0.8

19.2

23.3

35

042

208/230-3

197/254

10.3

 

77.0

1.90

12.2

14.7

 

25

0.8

13.0

15.6

25

460-3

414/506

5.1

 

39.0

1.00

 

6.1

7.4

 

15

0.7

6.8

8.1

15

 

 

 

 

 

575-3

518/633

4.2

 

31.0

0.80

 

5.0

6.1

 

15

N/A

N/A

N/A

N/A

 

208/230-1

197/254

18.3

 

109.0

3.00

21.3

25.9

 

40

1.07

22.4

26.9

45

048

208/230-3

197/254

12.4

 

88.0

3.00

15.4

18.5

 

30

1.07

16.5

19.6

30

460-3

414/506

6.4

 

44.0

1.70

 

8.1

9.7

 

15

1.07

9.2

10.8

15

 

 

 

 

 

575-3

518/633

4.8

 

34.0

1.50

 

6.3

7.5

 

15

N/A

N/A

N/A

N/A

 

208/230-1

197/254

25.0

 

169.0

3.40

28.4

34.6

 

50

1.07

29.5

35.7

60

060

208/230-3

197/254

17.3

 

123.0

3.40

20.7

25.0

 

40

1.07

21.8

26.1

40

460-3

414/506

6.7

 

49.5

1.80

 

8.5

10.2

 

15

1.07

9.6

11.2

15

 

 

 

 

 

575-3

518/633

5.8

 

40.0

1.60

 

7.4

8.8

 

15

N/A

N/A

N/A

N/A

 

208/230-1

197/254

28.8

 

169.0

4.30

33.1

40.4

 

60

1.07

34.8

42.0

70

070

208/230-3

197/254

17.3

 

137.0

4.30

21.6

25.9

 

40

1.07

23.3

27.6

40

460-3

414/506

9.0

 

62.0

2.50

11.5

13.7

 

20

1.07

12.6

14.8

20

 

 

 

 

575-3

518/633

6.6

 

49.0

2.20

 

8.8

10.5

 

15

N/A

N/A

N/A

N/A

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

FLA — Full Load Amps

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

HACR — Heating, Air Conditioning and Refrigeration

RLA

Rated Load Amps

 

 

 

 

 

HWR — Hot Water Reheat

 

 

 

 

 

 

 

 

 

 

 

 

 

PRE-START-UP

System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:

1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for 3 phase units.

2.Fuses, breakers and wire are correct size.

3.Low voltage wiring is complete.

4.Piping and system flushing is complete.

5.Air is purged from closed loop system.

6.System is balanced as required. Monitor if necessary.

7.Isolation valves are open.

8.Water control valves or loop pumps are wired.

9.Condensate line is open and correctly pitched.

10.Transformer switched to lower voltage tap if necessary.

11.Blower rotates freely — shipping support is removed.

12.Blower speed is on correct setting.

13.Air filter is clean and in position.

14.Service/access panels are in place.

15.Return-air temperature is between 40 to 80 F heating and 50 to 110 F cooling.

16.Air coil is clean.

17.Control field selected settings are correct.

26

Page 26
Image 26
Carrier RDS006-060, RVR, RHR, RVC, 50RHC specifications Pre-Start-Up, 50RDS, RHS, RVS Electrical Data