Carrier RVR Heating Cycle Analysis, Cooling Cycle Analysis, Flow Rate Gpm, Temp. Diff. Deg. F

Models: 50RHC RHS RVC RHR RVR RDS006-060 RVS

1 44
Download 44 pages 51.02 Kb
Page 44
Image 44
HEATING CYCLE ANALYSIS

HEATING CYCLE ANALYSIS

 

 

PSI

SAT

 

 

F

 

 

AIR

 

SUCTION

 

COIL

 

 

 

 

F

F

 

 

 

 

 

COMPRESSOR

 

EXPANSION

COAX

DISCHARGE

 

VALVE

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE

 

 

F

 

 

 

 

F

 

 

 

 

 

PSI

 

 

 

 

PSI

a50-8197.eps

WATER IN

 

WATER OUT

 

 

 

 

 

 

 

 

 

LOOK UP PRESSURE DROP IN TABLES 22-24

 

 

 

 

 

 

 

 

 

 

 

TO DETERMINE FLOW RATE

COOLING CYCLE ANALYSIS

PSISAT

°F

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE

 

AIR

 

COIL

°F

°F

EXPANSION

COAX

VALVE

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE

 

°F

 

 

 

°F

a50-8165

 

 

PSI

 

 

 

 

PSI

WATER IN

 

WATER OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUCTION

COMPRESSOR

DISCHARGE

LOOK UP PRESSURE DROP IN TABLES 22-24 TO DETERMINE FLOW RATE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

FLOW RATE (GPM) x

 

TEMP. DIFF. (DEG. F) x

 

FLUID FACTOR* =

(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE

=(DEG F)

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE

=(DEG F)

*Use 500 for water, 485 for antifreeze.

Copyright 2007 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

Catalog No. 04-53500007-01 Printed in U.S.A.

Form 50R-5SI

Pg CL-2

6-07

Replaces: 50R-4SI

Tab

5a

5a

 

 

 

 

 

 

 

 

 

 

 

 

 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 44
Image 44
Carrier RVR Heating Cycle Analysis, Cooling Cycle Analysis, Flow Rate Gpm, Temp. Diff. Deg. F, Fluid Factor* =, a50-8165