Turbomachinery Package Specification | Titan 250 Generator Set |
|
|
armature and a
The generator is supplied with a
Approximate Weight
Generator (Typical Open Drip Proof) | 45 000 kg (99,200 lb) |
Construction Types |
|
Open Drip Proof (OPD), Air Cooled | Standard |
Closed Air Circuit | Optional |
Closed Air Circuit, Air Cooled (CACA) | Optional |
Totally Enclosed | Optional |
Totally Enclosed Water Air Cooled (TEWAC) | Optional |
Generator |
|
Optional Voltage Ratings See Note (a) | 11,000, 12,470, or 13,800 VAC, |
Frequency Ratings | 50 or 60 Hz |
Number of Poles | 4 |
Number of Leads | 6 |
Connection | Wye |
Stator Windings | Form Wound |
Insulation | National Electrical Manufacturers Association |
| (NEMA) Class F |
Temperature Rise See Note (b) | NEMA Class B, |
Overload Capacity | |
| |
Overload Compliance | NEMA |
Short Circuit Capability | 300% For 10 seconds |
Rotor Balance | To 125% of Rated Speed |
Maximum Wave Form Deviation | 10% |
Maximum Harmonic Content | 3% |
Telephone Influence Factor (TIF) |
|
Balanced | 100 |
Residual | 75 |
Efficiency | The combined generator, exciter, and regulator |
| efficiency at full load is nominally 97%. |
Space Heater |
|
Voltage | 120, 220, 230, or 240 VAC |
Frequency | 50 or 60 Hz |
Phase | 1 Phase |
Vibration Monitoring |
|
Generator Bearing Driven End | Displacement Probes, X and Y axis |
Generator Bearing Exciter End | Displacement Probes, X and Y axis |
Notes: |
|
(a)Other voltages can be provided to meet specific customer requirements.
(b)A 80°C (144°F) temperature rise is based on the generator nameplate rating at 40°C (104°F) and a power factor of 0.8 for continuous duty service.
© 2008 Solar Turbines Incorporated. All rights reserved. | TPS250GS/908 - Preliminary |
16