Turbomachinery Package Specification | Titan 250 Generator Set |
|
|
10 Generator Control and Monitoring
10.1General Description
For generator control and monitoring, the Turbotronic 4 control system incorporates a Rockwell
•Automatic voltage regulation (AVR) - A constant generator output voltage is maintained
•Power factor (PF) control - A constant power factor is maintained when operating in parallel with a large power source
•Reactive power control - A constant reactive load is maintained when operating in parallel with a large power source
The following excitation control features are available:
•Under frequency limiting
•Over and under excitation limiting
•Reactive droop compensation
•
•
Protection features for the driver and driven equipment include:
•Field current limit
•Generator overcurrent
•Generator overvoltage
•Generator undervoltage
•Loss of excitation current
•Loss of operating power
•Loss of sensing
•Over excitation voltage
•Overfrequency
•Underfrequency
•Phase rotation error
•Reverse power
•Reverse volt amp reactive (VAR)
•Exciter (rotating) diode monitor
The protection features provided typically do not meet the requirements of power utility companies for the general protection of power distribution systems. This can only be done through the use of appropriately certified protective relay components with settings approved by qualified personnel based on a comprehensive analysis of the complete system.
© 2008 Solar Turbines Incorporated. All rights reserved. | TPS250GS/908 - Preliminary |
40