Turbomachinery Package Specification

Titan 250 Generator Set

 

 

Applicable Engineering Specifications

Solar’s Engineering Specification ES 9-224

Fuel, Air, and Water (or Steam) for Solar Gas

 

Turbine Engines

Solar’s Engineering Specification ES 1593

Guidelines for NEC Compliance of Solar Product

 

Lines: Class I, Group D, Division 1 and Division 2

Solar’s Engineering Specification ES 1762

Standards and Practices for Electrical Systems for

 

Gas Turbine Packages Installed In Hazardous

 

Areas (CENELEC/IEC Standards – European

 

ATEX Directive 94/9/EC)

Applicable Product Information Letters

 

Solar’s Product Information Letter PIL 058

Package Sound Levels

Solar’s Product Information Letter PIL 161

Lube Oil System Cleanliness

Notes:

(a)A pressure control valve regulates main lube oil supply pressure to 241 kPag (35 psig) when unit is at normal operating temperature.

(b)Prevailing winds must be considered to prevent the lube oil cooler from exhausting into the engine air inlet system or to take air in from the engine exhaust system. No airflow backpressure is allowed at the lube oil cooler face.

(c)The maximum total design pressure drop of the off skid oil cooler loop including supply and return lines shall not exceed 50 psid (345 kpad) at the design flow rate and an oil viscosity of 60 ssu (10.5 centistokes). No check valves are allowed in the oil cooler loop. This is recommended for all applications (but mandatory for units in cold climates), oil cooler supply, return and optional vent lines must slope from the oil cooler to the turbine package to facilitate draining when the unit is not operating.

(d)The heater is mandatory if unit ambient temperature is less than 10°C (50°F).

(e)The lube oil tank immersion heater ensures the lube oil tank temperature remains above 10°C (50°F) for starting in cold temperatures.

(f)The flame arrestor must be installed vertically at the end of the lube tank vent piping.

(g)Start-up strainers must be inspected after 100 hours of operation.

(h)An additional 246 L (65 gal) is required for package filters and piping. Additional oil will also be required to fill any offskid oil piping and vessels (if applicable).