Turbomachinery Package Specification | Titan 250 Generator Set |
|
|
On detection of a fire by the optional fire and gas detection system, the fire control panel activates the fire suppression system release solenoids located on the water mist suppression skid. On receipt of this signal, the solenoid actuated control heads activate the discharge valves on the water cylinders, releasing a water mist into the enclosure. A pressure switch in the water mist discharge piping transmits an electrical signal to the fire control panel to activate a release solenoid to close
When installed outdoors, weatherproof fire cylinder cabinets are available to house the extinguishing agent. The cabinets are equipped with service doors. The manual pull levers are routed by cable to the exterior wall of the cabinet.
Figure 23. Typical CO2 Fire Suppression Cylinders and CabinetsFigure 24. Typical Water Mist Fire Suppression Cylinders and Cabinet© 2008 Solar Turbines Incorporated. All rights reserved. | TPS250GS/908 - Preliminary |