Turbomachinery Package SpecificationTitan 250 Generator Set
Table 10. Air Inlet System SpecificationsAir Inlet System
Pressure Drop | Less Than 102 mm (4 in.) H2O with a Clean Air Filter |
Ducting Loads | Should Not Be Applied In Any Direction |
Prefilter and Barrier Inlet Air Filter |
|
Pressure Drop |
|
Clean | 44 mm (1.75 in.) water |
Fouled | 127 mm (5 in.) water |
| |
Fluid | |
Air Quality | See Note (a) |
Minimum/Maximum Regulated Pressure Range | 552 to 758 kPag (80 to 100 psig) |
Intermittent Flow Rate | 0.5 nm3/min (18 scfm) |
Pressure Drop (Clean) | 25 mm (1.0 in.) water |
| |
Pressure Drop (Clean) | 53 mm (2.1 in.) water |
Construction Materials |
|
Prefilter/Barrier | Carbon Steel (Standard) |
| 316L Stainless Steel (Optional) |
Insect Screen | Carbon Steel (Standard) |
| 316L Stainless Steel (Optional) |
Self Cleaning Barriers | Carbon Steel (Standard) |
| 316L Stainless Steel (Optional) |
316L Stainless Steel (Standard) | |
Air Inlet Silencer | Carbon Steel (Standard) |
| 316L Stainless Steel (Optional) |
Air Inlet Ducting | Carbon Steel (Standard) |
| 316L Stainless Steel (Optional) |
Air Inlet Support Structure | Carbon Steel (Standard) |
Applicable Product Information Letters |
|
Solar’s Product Information Letter PIL 054 | OSHA Noise Requirements |
Solar’s Product Information Letter PIL 178 | Salt Ingress Protection for Gas Turbines |
Notes: |
|
(a)The particle size in the air stream should not exceed 10μm. Since it is impractical to remove 100% of all particles larger than 10μm, this is defined as ß10 > 100, or 99% efficient. Oil or hydrocarbon content should not exceed 1 ppm. The dew point at line pressure shall be at least 6°C (10°F) below the minimum temperature to which any part of the air system is exposed or between 1.6°C and 60°C (35°F and 140°F). Air should be free of all corrosive contaminants, hazardous gases, flammables, and toxics.