Turbomachinery Package Specification | Titan 250 Generator Set |
|
|
Fluid | |
Air Quality | See Note (d) |
Minimum/Maximum Regulated Pressure Range | 689 to 1379 kPag (100 to 200 psig) |
Pilot Air Filter | 10 micron |
Construction Materials |
|
Piping, Manifolds, and Tubing | 316L Stainless Steel |
Applicable Engineering Specifications |
|
Solar’s Engineering Specification ES | Fuel, Air, and Water (or Steam) for Solar Gas |
| Turbine Engines |
Solar’s Engineering Specification ES 1593 | Guidelines for NEC Compliance of Solar Product |
| Lines: Class I, Group D, Division 1 and Division 2 |
Solar’s Engineering Specification ES 1762 | Standards and Practices for Electrical Systems for |
| Gas Turbine Packages Installed In Hazardous |
| Areas (CENELEC/IEC Standards – European |
| ATEX Directive 94/9/EC) |
Applicable Product Information Letters |
|
Solar’s Product Information Letter PIL 148 | LPG and NGL Fuels |
Solar’s Product Information Letter PIL 162 | Recommendations for the Sourcing, Handling, |
| Storage and Treatment of Fuels for Solar Gas |
| Turbines |
Solar’s Product Information Letter PIL 176 | Siloxanes in Gas Fuel |
Notes: |
|
(a)The gas fuel system is designed to operate with fuels that comply with Solar’s Engineering Specification ES
(b)Fuel pressure and flow requirements can be affected by several factors such as; fuel temperature, fuel lower heating value, air inlet temperature, fuel composition, fuel specific gravity, engine injector type, inlet duct loss, relative humidity, site elevation, and piping length and diameter. Based on site conditions, minimum fuel pressure and flow requirements may be less than stated values. Please contact Solar Turbines for
(c)Fuel must have a differential temperature ( T) of at least 27°C (50°F) above fuel dew point temperature.
(d)The particle size in the air stream should not exceed 10μ. Since it is impractical to remove 100% of all particles larger than 10μ, this is defined as ß10 > 100, or 99% efficient. Oil or hydrocarbon content should not exceed 1 ppm. The dew point at line pressure shall be at least 6°C (10°F) below the minimum temperature to which any part of the air system is exposed or between
© 2008 Solar Turbines Incorporated. All rights reserved. | TPS250GS/908 - Preliminary |
23