Turbomachinery Package Specification

Titan 250 Generator Set

 

 

Figure 20. Typical Generator Metering Panel10.2.7Generator Vibration and Temperature Monitoring

X and Y proximity probes are mounted in the generator exciter and driven-end bearings. These probes are monitored continuously by the control system. Alarm and shutdown levels are set to protect the generator from excessive vibration levels

Resistance temperature devices (RTDs) are mounted in the generator exciter and driven end bearings. Two RTDs are also imbedded in each of the three stator-winding phases. One RTD is connected to the control system and the other is provided as a spare. Alarm and shutdown levels are set to protect the generator from excessive temperature levels.

10.2.8Redundant Combined Generator Control Module (Optional)

A second CGCM can be provided to function as a hot backup to the primary CGCM. The system is configured for automatic transfer to the second CGCM in the event the primary CGCM fails. All control, protection, and monitoring features of the primary CGCM are duplicated in the second CGCM. Control can also be manually transferred between the CGCMs.

Table 8. Generator Specifications

Voltage Regulation

Voltage Regulator

Solid State

Phase Sensing

Three Phase (Standard)

 

Single Phase Sensing (Optional)

Voltage Adjustment Range

±10% With a Voltage Resolution of 0.1%

Steady-State Voltage Regulation

0.25% From No Load to Rated kVA

Reactive Load Sharing

Within 5% of Nameplate Rating

Cross-Current Compensation

Optional

Voltage Drift

See Note (a)

Generator Breaker Synchronization

 

Generator Voltage

To Close Breaker, Generator Voltage Must be

 

Within ± 1.0 Percent of Bus Voltage

Generator Phase

To Close Breaker, Generator Phase Must be Within

 

± 10 Degrees of Bus Phase

Generator Frequency

To Close Breaker, Generator Frequency Must Be

 

Within ± 0.01 Hz of bus frequency

Generator Ready to Load

Twenty seconds after generator set attains 90

 

percent speed

Notes:

(a)The change in voltage will not exceed 1.0% over a 30-minute period when the generator is operating at rated voltage, power factor of 0.8 to 1.0, and with a constant load between no load and full rated load.

© 2008 Solar Turbines Incorporated. All rights reserved.

TPS250GS/908 - Preliminary