Chapter 2 Preparing for Installation

Site Requirements

Site Requirements

This section provides site power requirements for the Cisco 7609 Internet Router. You should verify the site power prior to installing the switch. Power requirements vary for each switch; ensure that you verify the site power for the type of switch you are installing.

For EMI recommendations, refer to the Site Preparation and Safety Guide.

Environmental Requirements

Insure adequate spacing between racks using the information in Table 2-1. Keep all of the vents clear of obstructions, including dust and foreign conductive material, and away from the exhaust ports of other equipment.

Table 2-1 Chassis Airfow Requirements

 

 

 

 

Minimum

Minimum

 

 

Airflow

Air Filter

Clearance

Horizontal

Chassis Model

Airflow Intake

Exhaust

Option

(walls)

Separation

 

 

 

 

 

 

OSR-7609

Front, rear

Front, rear, left

No

6 in (15 cm)

12 in (30.5)

(Figure 1-2)

 

side, right side

 

 

 

 

 

 

 

 

 

Heat dissipation is an important consideration for sizing the air-conditioning requirements for an installation. The power and heat associated with a Cisco 7609 Internet Router varies based upon these considerations:

Power supply type

Module types and quantities

Average traffic levels

Unless otherwise noted, the information in Table 2-2and Table 2-3assumes worst-case conditions (with GBICs and port adapters installed, if applicable). Typical numbers are approximately 30 percent below the numbers listed here. See Table 2-4for a sample calculation of a switch configuration.

 