Chapter 2 Preparing for Installation

Site Requirements

Table 2-4provides a sample calculation of power and heat dissipation for the following switch configuration:

Cisco 7609 Internet Router chassis (including AC-input power supplies)

Two WS-X6K-S2U-MSFC2 supervisor engines

One Switch Fabric Module

Two 4-port OC-12 POS modules

Two 8-port OC-3 POS modules

Table 2-4 Sample Calculation

 

AC-Input

DC-Output

 

 

Input Current

 

 

 

 

 

 

 

Model Number/

Power

Power

Heat Diss.

90 VAC

120 VAC

180 VAC

240 VAC

Module Type

(Watts)

(Watts)

(BTU/HR)

(Amps)

(Amps)

(Amps)

(Amps)

 

 

 

 

 

 

 

 

Cisco 7609 Internet Router

124

50

422

1.37

1.03

0.69

0.52

chassis (with fans)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS-X6K-S2U-MSFC2

322

258

1098

3.58

2.68

1.78

1.34

 

 

 

 

 

 

 

 

WS-C6500-SFM

146

117

500

1.63

1.22

0.81

0.61

Switch Fabric Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OSM-4OC12-POS-MM

502

402

1714

5.58

4.18

2.78

2.10

4-port OC-12 module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OSM-8OC3-POS-MM

374

300

1280

4.16

3.12

2.08

1.56

8-port OC-3 module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

1468

1127

5014

16.32

12.23

8.14

6.13

 

 

 

 

 

 

 

 

 

 

Cisco 7609 Internet Router Installation Guide

 

 

 

 

 

 

OL-5079-04

 

 

2-7

 

 

 

Page 39
Image 39
Cisco Systems 7609 manual WS-X6K-S2U-MSFC2