22-29
Cisco ONS 15454 Procedure Guide, R7.0
November 2007
Chapter22 DLPs A500 to A599
DLP- A530 Install the Tie-Down Bar
Step1 Double-click the Ethernet card where you want to delete the RMON alarm thresholds.
Step2 In card view, click the Provisioning > Ether Ports > RMON Thresholds tabs.
Note For the CE-Series, click the Provisioning > Ether Ports > RMON Thresholds tabs or
Provisioning > POS Ports > RMON Thresholds tabs.
Step3 Click the RMON alarm threshold you want to delete.
Step4 Click Delete. The Delete Threshold dialog box appears.
Step5 Click Yes to delete the threshold.
Step6 Return to your originating procedure (NTP).
DLP-A530 Install the Tie-Down Bar
Step1 Align the ends of the tie-down bar with the four screw holes located 1 RU below the ONS 15454.
Figure 22-8 shows the tie-down bar, the ONS 15454, and the rack.
Purpose This task installs the tie-down bar used to secure cabling on the rear of the
ONS 15454. The tie-down bar can be used to provide a diverse path for
redundant power feeds and cables.
Tools/Equipment Tie-down bar
Screws (4)
Prerequisite Procedures DLP-A5 Mount the Shelf Assembly in a Rack (One Person), page 17-5
DLP-A6 Mount the Shelf Assembly in a Rack (Two People), page 17-6
Required/As Needed As needed
Onsite/Remote Onsite
Security Level None